Definition And Range Of Parameters - Smartgen HAT162 User Manual

Ats controller
Table of Contents

Advertisement

No.
Items
18
1# Close Input
19
2# Close Input
20
Common Port
Communication
LINK
Port
F1
Fuse
F2
Fuse

7. DEFINITION AND RANGE OF PARAMETERS

No.
Items
1
AC System
2
S1 Normal Delay
3
S2 Normal Delay
4
S1 Abnormal Delay
5
S2 Abnormal Delay
HAT162 ATS Controller User Manual
Function Description
Detect 1# breaker close
status,
auxiliary
input.
Detect 2# breaker close
status,
auxiliary
input.
GND
Communicate with PC and
used for program update
Table 6 Parameters Definition and Range Table (1)
Range
Default
(1-4)
1
(1-7)
2
(1-7)
2
(1-7)
2
(1-7)
2
contact
Ground is active.
contact
Ground is active.
Used with SG72 adaptor.
Rated 10A 250V.
Rated 10A 250V.
1: 3 Phase, 4 Wire (3P4W)
2: Single Phase, 2 Wire (1P2W)
3: 3 Phase, 3 Wire (3P3W) (special order required)
4: 2 Phase, 3 Wire (2P3W)
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined (Default: 5s)
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined (Default: 5s)
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined (Default: 5s)
1: 1s
2: 5s
Remark
Description
Page 10 of 21