Definition And Range Of Parameters; Parameter Contents And Range - Smartgen APC615 User Manual

Pump unit controller
Table of Contents

Advertisement

7

DEFINITION AND RANGE OF PARAMETERS

7.1 PARAMETER CONTENTS AND RANGE

No.
Items
Language
1
Language
Timers
1
Start Delay
2
Return Delay
3
Preheat Delay
4
Pre-start Fuel Time
5
Cranking Time
6
Crank Rest Time
7
Safety On Delay
8
Start Idle Time
9
Warming Up Time
10
Cooling Time
11
Stop Idle Time
12
ETS Solenoid Hold
13
Wait for Stop Time
14
After Stop Time
15
Fuel
Pre-supply (0-12)h
Parameter
Default
(0-2)
0
(0-3600)s
1
(0-3600)s
1
(0-3600)s
0
(0-3600)s
1
(3-60)s
8
(3-60)s
10
(0-3600)s
10
(0-3600)s
0
(0-3600)s
10
(0-3600)s
10
(0-3600)s
0
(0-3600)s
20
(0-3600)s
0
(0-3600)s
0
2
Description
0: Simplified Chinese; 1:English; 2:Other
Time from remote start signal is active to start
the pump unit.
Time from remote stop signal is deactivated to
stop the pump unit.
Time of pre-powering heat plug before starter
is powered up.
Fuel relay output time before starter power on.
Time of starter powers up.
(If diesel driven pump unit is enabled, this time
also can be cranking time of diesel driven
pump unit).
The waiting time before second power up
when engine starts fail.
(If diesel driven pump unit is enabled, this time
also can be crank rest time of diesel driven
pump unit).
Alarms for low oil pressure, high temperature,
under speed, under frequency/voltage, charge
fail are deactivated during "Safety On Delay".
Idle running time of the pump unit when
starting.
Warming time between the pump unit take load
and high speed running.
Radiating time before stop the pump unit, after
it unloads.
Idle running time when pump unit stop.
Stop electromagnet's power on time when
pump unit is stopping.
(If diesel driven pump unit is enabled, this time
also can be stop output time of diesel driven
pump unit).
Time between ending of pump unit idle delay
and stopped when "ETS Solenoid Hold" is set
as 0;
Time between ending of ETS delay and
stopped completely when "ETS Hold output
time" is not 0.
Time between pump unit stopped and standby.
When unit is in standby status and the output

Advertisement

Table of Contents
loading

Table of Contents