7 DEFINITION AND RANGE OF PARAMETERS

7.1 PARAMETER CONTENTS AND RANGES

No.
Items
Timer Setting
1
Start Delay
2
Stop Delay
3
Preheat Delay
4
Cranking Time
5
Crank Rest Time
6
Safety On Delay
7
Start Idle Time
8
Warming Up Time
9
Cooling Time
10
Stop Idle Time
ETS
Solenoid
11
Hold
12
Fail to Stop Delay
13
After Stop Time
Engine Setting
1
Engine Type
2
Flywheel Teeth
APC715 Pump Unit Controller User Manual
Table 13 Parameter Contents and Ranges
Parameter
Default
(0-3600)s
1
(0-3600)s
1
(0-3600)s
0
(3-60)s
8
(3-60)s
10
(0-3600)s
10
(0-3600)s
0
(0-3600)s
10
(0-3600)s
10
(0-3600)s
0
(0-3600)s
20
(0-3600)s
0
(0-3600)s
0
(0-39)
0
(10-300)
118
Description
Time from remote start signal is active to
start the pump unit.
Time
from
remote
deactivated to stop the pump unit.
Time of pre-powering heat plug before
starter is powered up.
Time of starter power up
The waiting time before second power up
when engine start fail.
Alarms
for
low
oil
temperature,
under
frequency/voltage, charge failure are
inactive.
Idle running time of the pump unit when
starting.
Warming time between the pump unit
take load and high speed running.
Radiating time before stop the pump unit,
after it unloads.
Idle running time when pump unit stop.
Stop electromagnet's power on time
when pump unit is stopping.
Time between ending of pump unit idle
delay and stopped when "ETS output
time" is set as 0;
Time between ending of ETS hold delay
and stopped when "ETS output time" is
not 0.
Time between pump unit stopped and
standby.
Default: Conventional engine (not J1939)
When connected to J1939 engine, choose
the corresponding type.
Tooth number of the engine, for judging
start
signal
is
pressure,
high
speed,
under
Page 28 of 62