7 DEFINITION AND RANGE OF PARAMETERS

7.1 PARAMETER SETTING CONTENTS AND RANGE

No.
Items
P00
Mains Normal Delay (0-3600)s
Mains
Abnormal
P01
Delay
Mians Under Volt
P02
Value
Mains
Over
P03
Value
P04
Mains Options
P05
Start Delay
P06
Stop Delay
P07
Start Attempts
P08
Pre Heating
P09
Cranking Time
P10
Crank Rest Time
P11
Safety On Delay
P12
Start Idle Delay
P13
Warming Up Time
P14
Cooling Time
P15
Stop Idle Delay
P16
ETS Solenoid Hold
P17
Wait for Stop
MGC300 Genset Controller
Table 7 Controller Configuration Parameters
Parameter Range Default
(0-3600)s
(30-6000)V
Volt
(30-6000)V
(0-1)
(0-3600)s
(0-3600)s
(1-10) times
(0-300)s
(3-60)s
(3-60)s
(1-60)s
(0-3600)s
(0-3600)s
(3-3600)s
(0-3600)s
(0-120)s
(0-120)s
Version 1.1
MGC300 Genset Controller User Manual
10
Check time duration for Mains voltage from
abnormal to normal or from normal to
5
abnormal to be used for ATS transfer.
If the voltage sample is lower than it, Mains
under voltage is considered; When it is set
184
30V, under voltage signal shall not be
detected; return difference is 10V;
If the voltage sample is higher than it, Mains
over voltage is considered; When it is set
276
60000V, overvoltage signal shall not be
detected; return difference is 10V;
0
0: AMF
Time duration from mains abnormal or
1
remote start signal is active to genset
startup.
Time duration from mains normal or remote
1
start signal is deactivated to genset stop.
It is maximum start attempts when starter
3
fails to start. When it reaches set attempts
controller shall send out start failure signal.
Pre-heating
0
before starter is powered on;
8
Time for starter to be energized every time.
The waiting time before second power up
10
when engine start fails.
Alarms for low oil pressure, temp. high,
10
under speed, under frequency and under
voltage are deactivated.
0
Time for genset idle running at starting;
Warming-up time before breaker close after
10
high speed running for genset.
Radiating time before genset stop after
10
genset is unloaded.
0
Time for genset idle running at stopping;
The time for Stop electromagnet to be
20
energized before genset stop.
Time from idle delay to complete stop when
0
ETS stop output is set to 0; when the output
time is not 0s; it's time from ETS stop end to
2020-01-04
Description
1: Display Only
plug
pre-energization
Page 16 of 27
time