• Rack connection to the building structure.
Table 29 on page 91
provides the rack requirements and specifications.
Table 29: Rack Requirements and Specifications
Rack Requirement
Guidelines
Rack type
A U is the standard rack unit defined by the Electronic Components Industry Association
(http:/
You can mount the device on a rack that provides bracket holes or hole patterns spaced at
1U (1.75 in. or 4.45 cm) increments and meets the size and strength requirements to
support the weight.
Mounting bracket
The holes in the mounting brackets are spaced at 1U (1.75 in. or 4.45 cm) so that the
hole spacing
device can be mounted in any rack that provides holes spaced at that distance.
Rack size and
Ensure that the:
strength
Rack connection to
Secure the rack as follows:
building structure
/www.ecianow.org).
Rack complies with the size and strength standards of a 19-in. rack as defined by the
Electronic Components Industry Association
Rack rails are spaced widely enough to accommodate the external dimensions of the
device chassis. Ensure also that the outer edges of the front mounting brackets extend
the width of the chassis to 19 in. (48.2 cm).
Rack is strong enough to support the weight of the device.
Spacing of rails and adjacent racks provides for proper clearance around the device and
rack.
Secure the rack to the building structure.
If your geographical area is earthquake-prone, secure the rack to the floor.
Secure the rack to the ceiling brackets as well as wall or floor brackets for maximum
stability.
(http:/
/www.ecianow.org).