Troubleshooting on saving project data
Symptom
Check point
Unable to save project data.
Is a recording setting written?
Is the operating status of the recording function 'operating'?
(Page 63 Operating status)
Does an SD memory card satisfy the following conditions
when it is specified as the save destination for the recording
file?
• It is inserted in a recorder module/camera recorder module.
• An available one is used.
• There is free space.
Does a file server satisfy the following conditions when it is
specified as the save destination for the recording file?
• The file server is running.
• There is no problem in the connection route.
• The user name or password is correct.
Is a recorder module or camera recorder module with a
firmware version supporting the project data saving function
used as the main one?
Is an RnCPU or RnENCPU used as a CPU module?
Unable to automatically
Is "Automatic Saving at Recording Start" set to "Save" under
save project data when
"Project Data Saving Setting" in the module parameter of a
recording starts.
module set as the main one?
(Page 99 Project data saving setting)
Unable to save project data
Is an operation performed on the buffer memory of the
by operating the buffer
corresponding recording setting number of a module set as
memory.
the main one in a program, an engineering tool, or external
device, etc.?
(Page 232 Project data saving specification area
(Un\G14080 to 14199))
Corrective action
Write the recording setting.
• Switch the operating status to 'operating.'
For the operation method, refer to the following:
Page 65 Operation of the recording function
• Check the SD memory card.
• Replace or initialize the SD memory card.
(MELSEC iQ-R System Recorder User's Manual (Startup))
• Start the file server.
• Check if there is any problem in the connection route to the
file server.
• Review the user name and password for the file server in the
recording setting.
Use a recorder module or camera recorder module with a
firmware version supporting the function.
• If neither is used, the project data saving function does not
work.
• Read project data used to play a recording file from the CPU
module or prepare it separately.
Set "Automatic Saving at Recording Start" to "Save" under
"Project Data Saving Setting" in the module parameter of the
module.
Perform an operation on the buffer memory of the
corresponding recording setting number of the module.