Error code
Error name
3032H
Recording Setting Error
3033H
Recording Setting Error
3034H
Recording Setting Error
3040H to 3044H
Control CPU Communication
Error
3045H
Control CPU Communication
Timeout
3050H to 3064H
Module Error
3070H to 3071H
Module Error
3080H to 308AH
Module Error
3090H
Module Error
3092H to 309AH
Module Error
30A0H to 30A2H
Module Error
30A8H to 30AAH
Module Error
Error description
• The mounting position and control CPU of
the recorder module are different from the
ones of the system parameter at the
recording setting.
• The mode of the module parameter is not
set to "Online" or the module status
setting of the system parameter (I/O
assignment setting) is set to "Empty" in
some Main.
A recording setting file which is not
supported by the firmware version of the
target recorder module was written.
The link-direct device, module access
device, or CPU buffer memory access
device specified for collection does not have
an access destination or is out of range.
Failed to communicate data with the control
CPU module.
The data communication with the control
CPU module has timed out.
Corrective action
• Please check the mounting position and control CPU
of the recorder module.
• Please check the system parameter and actual
system configuration.
• Please review the recording operation setting of the
module parameter and set the number of modules of
"Main" to one.
• Please remove the module from Main where the
module status setting of the system parameter (I/O
assignment setting) is set to "Empty".
Please check the version of the recorder module, use a
compatible product, and then write the recording file
again.
• Please review the device/label sampling target
setting in the recording setting.
• If the Device/Label sampling target setting is set to
the Device/Label batch specification, review the
program used to set recording.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the recorder module. Please
consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the recorder module. Please
consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the recorder module. Please
consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the recorder module. Please
consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the recorder module. Please
consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the recorder module. Please
consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the recorder module. Please
consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the recorder module. Please
consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the recorder module. Please
consult your local Mitsubishi representative.
5 TROUBLESHOOTING
5.6 Recorder Module
5
173