Error Code List - Mitsubishi Electric NZ2GFCE-60DAV8 User Manual

Cc-link ie field network digital-analog converter module (e-con type)
Table of Contents

Advertisement

10.2
This section describes error codes.
Error codes are classified by error number as follows.
Error code
0000H to 0FFFH, 1F00H to 1F40H, D52BH
D000H to DFFFH (D52BH excluded)
List of error codes (0000H to 0FFFH, 1F00H to 1F40H, D52BH)
The errors are classified into the following three types:
Classification
Major error
Moderate error
Minor error
If any of these errors occurs, check that the D LINK LED lights up, and take the corrective actions corresponding to the error
code with the list below.
Error code
(hexadecimal)
0010H
010H
*1
0130H
0140H
0160H
*1
062H
10 TROUBLESHOOTING
92

10.2 Error Code List

Downloaded from
ManualsNet.com
Error Code List
Classification
Errors relating to the D/A converter module
Errors relating to the CC-Link IE Field Network
(communication error)
Description
This error is a sign that recovery is impossible, with the RUN LED turning off.
This error is a sign that the module cannot continue to operate, with the ERR. LED turning on.
This error is a sign that the module can continue to operate, with the ERR. LED flashing.
Classification
Error name
Major error
Hardware failure
Moderate error
Range setting out-
of-range
Moderate error
Non-volatile
memory data error
(parameter)
Minor error
Non-volatile
memory data error
(error history)
Minor error
Remote buffer
memory access
error
Moderate error
Alert output upper/
lower limit value
inversion
search engine
Description and cause
Module hardware error
The value set in Range setting (CH1 to CH4)
(address: 0103H) or Range setting (CH5 to
CH8) (address: 0104H) is out of the range.
 indicates the number of the channel that has
been incorrectly set.
The parameter data stored in the non-volatile
memory are abnormal.
The error history data stored in the non-volatile
memory are abnormal.
A buffer memory area other than the remote
buffer memory areas has been accessed using
the REMFR/REMTO instruction.
The alert output lower limit value has been set
equal to or greater than the alert output upper
limit value in CH1 Alert output upper limit value
(address: 0108H) to CH8 Alert output lower
limit value (address: 0117H).
 indicates the number of the channel where
an error has occurred.
Reference
Page 92 List of error codes (0000H to 0FFFH,
1F00H to 1F40H, D52BH)
Page 94 List of error codes (D000H to DFFFH
(D52BH excluded))
Action
Turn off and on the module power supply.
If this error persists, the failure of the module is
a possible cause. Please consult your local
Mitsubishi representative.
Set a value again in Range setting (CH1 to
CH4) (address: 0103H) or Range setting (CH5
to CH8) (address: 0104H).
• To set the parameters of the non-volatile
memory back to their default, change
Parameter area initialization command
(address: 1002H) as follows: Not
commanded (0)Commanded (1)Not
commanded (0).
• Set the parameters again.
• Take measures to reduce noise, such as
using a shield wire for connection.
• If this error persists, the failure of the module
is a possible cause. Please consult your
local Mitsubishi representative.
• The module will be automatically recovered
immediately after the error occurs. Note that
the error history of the errors that have
occurred will be lost.
• Take measures to reduce noise, such as
using a shield wire for connection.
• If this error persists, the failure of the module
is a possible cause. Please consult your
local Mitsubishi representative.
Correct the setting data of the REMFR/REMTO
instruction to access the remote buffer
memory.
Correct the settings of CH1 Alert output upper
limit value (address: 0108H) to CH8 Alert
output lower limit value (address: 0117H) so
that the alert output lower limit value is smaller
than the alert output upper limit value.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gfce-60dai8

Table of Contents