Saving detail setting

Window
Click the [Detail] button in the saving path setting.
Displayed items
Item
Saving
Saved Data Upper Limit (1 to 999)
Operation
Operation at Saved Data Upper Limit
Setting
Saving Path
Setting Method
Format Setting
(1) Simple
specification
(1)
Add File Saving Trigger Date (yyyymmdd)
Add File Saving Trigger Time (hhmmss)
Description
Set the upper limit of saved recording files.
Select an operation performed when the upper limit of saved recording
files is exceeded.
• Save data by deleting the one with the oldest timestamp: A recording
file with the oldest time stamp is deleted and a new file is saved.
• Discard Data and Continue Sampling: A new recording file is not saved,
and data is discarded. In addition, a saving error occurs. (Page 86
If saving a file fails)
Select "Simple Specification" or "Detailed Specification."
• Simple Specification: To set only whether to add the date and time
when a file saving trigger is satisfied to a file name.
• Detailed Specification: To set whether to add the following items to a file
name:
Date and time (when a file saving trigger is satisfied or a recording file is
*1
saved)
Numerical value data (data in the buffer memory when a file saving
trigger is satisfied)
Any character strings
Select the checkbox to add the date and time when a file saving trigger
occurs to a file name.
(Example) February 23, 2019: 20190223
Select the checkbox to add the time when a file saving trigger occurs to a
file name.
(Example) 18:53:04: 185304
3 RECORDING SETTING
(2)
139
3.5 Saving Path Setting
3

Advertisement

Table of Contents
loading

Table of Contents