DISPLAY MODULE AND OFFICE CONFIGURATION EDITOR
_________________________________________________________________________________________________________
6. The uploading status will show until complete. Once complete, the message MEF file
uploaded successfully will display.
3.4.2.5 Change the MCF on CPU III via USB
Perform the following actions:
1. Insert USB Drive in the USB slot on the front of the Display.
2. If Maintainer security has been enabled, enter the password. The password is case
sensitive. If security is not enabled, proceed to step 3.
3. Connect an Ethernet cable between the Laptop port on the Display and the Laptop port
of the CPU III module.
4. You will need to verify that the Display is set up as a Client instead of a Server, to do so,
access the Laptop Ethernet Port menu Program View > 3) Display Settings > Laptop
Ethernet Port.
5. Select Client if Display is configured as Server.
SIG-00-22-02
Version: B.1
Figure 3-70 WebUI, GCP Menu – Upload Status

Figure 3-71 Ethernet Menu

3-46
JUNE 2022 (Revised September 2022)