Siemens Perfect Harmony GH150 Function Manual

Operator panel with touch screen air-cooled mv converters
Hide thumbs Also See for Perfect Harmony GH150:

Advertisement

Quick Links

Function Manual
Operator panel
with touch screen
for SINAMICS Perfect Harmony GH150,
air-cooled MV Converters
12/2022
www.siemens.com

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Perfect Harmony GH150

  • Page 1 Function Manual Operator panel with touch screen for SINAMICS Perfect Harmony GH150, air-cooled MV Converters 12/2022 www.siemens.com...
  • Page 3 Introduction Safety notes System configuration and hardening Product overview Operator panel for SINAMICS Operator panel configuration Perfect Harmony GH150 air- cooled MV Converters HMI App screen description Function Manual Installation, update, backup and recovery Password management Service and support List of abbreviations/ acronyms HMI version: V02.20.03.00...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Connecting to operator panel..................... 23 5.4.1 Webserver activation ......................23 5.4.2 Importing certificate ......................24 5.4.3 Manual login mode......................32 5.4.4 Automatic login mode ....................... 36 Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 6 Backing up and recovery ....................107 Password management ........................123 Password management....................123 Service and support........................... 127 List of abbreviations/acronyms......................129 List of abbreviations/acronyms ..................129 Index ..............................131 Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 7: Introduction

    This function manual provides a summary of all HMI App V2.2 relevant information required to operate SINAMICS Perfect Harmony GH150 air-cooled converters under normal and safe conditions. All described HMI functions can only work with SINAMICS MV Firmware V5.2.4 or higher versions.
  • Page 8 Industrial PC is called "IPC" in these instructions. SIMATIC IPC277E and operator panel are interchangeably used for naming. The Human Machine Interface application software is called "HMI App" for short. Microsoft Windows operating system is called "Windows" for short. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 9: Safety Notes

    Qualified personnel Only qualified personnel may perform work on SINAMICS Perfect Harmony GH150 operator panel. For the purpose of this documentation, qualified personnel mean people who fulfill the following requirements: •...
  • Page 10: Security Information

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
  • Page 11 Siemens customer service. An incident handling process will be initiated. Please nominate a cybersecurity responsible within your organization as contact point for incident handling process. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 12 2.5 Security recommendations Other softwares SIMATIC IPC277E with HMI App used in SINAMICS Perfect Harmony GH150 MV converters is by default protected by Microsoft Defender Anti-Virus, Application Whitelisting (set in Windows Application Firewall), malicious software removal tool for Windows and further comprehensive hardening measures.
  • Page 13: System Configuration And Hardening

    IPC. A warning is also issued if programs attempt to change important Windows settings. Configure the Security Center corresponding to the requirements. In addition, the Siemens CERT guidelines (https://www.cert.siemens.com/) are applied to the device. Whitelist The basic philosophy of whitelisting is that all applications are mistrusted, unless they have been classified as trustworthy after an appropriate check.
  • Page 14: Personal Data

    External keyboard Siemens strongly recommends that you use an external keyboard with USB interface (either USB 2.0 or USB 3.0) to user-friendly complete any type of tasks performed on SIMATIC IPC277E during commissioning or troubleshooting process. When an HMI image needs to be installed, an external keyboard is mandatorily required.
  • Page 15: Product Overview

    HMI App software HMI App is running via Windows operating system equipped on SIMATIC IPC277E. With HMI App running, the panel displays like this: Figure 4-2 Operator panel description Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 16 "Updating Windows (Page 102)" in this manual. HMI App Refer to the section entitled "HMI App screen description" for HMI App function and operation. See also HMI App screen description (Page 55) Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 17: Network Connection

    • Infeed CU320-2: The X127 port of the infeed CU connects to the p1 port of the Scalance. • Vector CU320-2: The X127 port of the vector CU connects to the p2 port of the Scalance. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 18: Hmi App Starting Screen

    The "Home" screen displays the following information about the initial status of the converter: • Actual values of the converter • The current status of the converter. The details of this screen is in Section "Home" screen (Page 55). Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 19: Operator Panel Configuration

    In addition to having the readable rights of Observer account, Administrator account has more advanced writing rights including the following: • Change and save parameters’ values • Change IP address • Change accounts’ password Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 20: Changing Account

    • Tap on "Observer" or "Administrator" in the header of screen page "Home". • Tap on "Login" or "Logout" in the local control area of screen page "Home". Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 21: Login As Administrator

    3. Confirm the password by tapping on "Confirm". If the password is wrong, the panel will switch to "Observer" account. Note The dual circuit feature for GH150 converters will be delivered soon. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 22: Logging Off From The Accounts/Logging In As Observer

    Switching account from Administrator to others while motor running is forbidden. If this is attempted, the following alert window will pop up: Figure 5-5 Alert window when logging off from Administrator Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 23: Passwords For Observer And Administrator

    Passwords for observer and administrator Webserver Administrator password is pre-set when the converter is delivered. Siemens strongly recommends the following protective measues when users set password: • Change the given password. • Regularly update password to increase the security level.
  • Page 24 • Use STARTER If the password is lost or reset. Figure 5-7 Set password via STARTER Figure 5-8 Set password via STARTER (cont.) See also Password management (Page 123) Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 25: Connecting To Operator Panel

    In the project navigator, right click Drive_unit and select Web server in the popup menu. Figure 5-9 Project navigator In the Web Server Configuration window, do the following settings: Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 26: Importing Certificate

    When SIMATIC IPC277E is connected to the CU for the first time, users will be asked to import the certificate into IPC when the connecting screen shows as the following. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 27 5.4 Connecting to operator panel Figure 5-11 HMI connecting to CU It is either happened when creating a new CF card or the IP address of CU having been changed. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 28 (AgentAdmin), referring to the section entitled "Password management (Page 123)". Figure 5-12 Switch to AgentAdmin account 2. Run Internet Explorer as an administrator. Figure 5-13 Run Internet Explorer as administrator Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 29 Figure 5-14 Certificate not secure 4. A guidance page will show. Click "Certificate error" on the right side of browser address input box. Figure 5-15 Certificate installation guide Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 30 5.4 Connecting to operator panel 5. A pop-up window will appear. Click "View certificates". Figure 5-16 Certificate details 6. The information of certificate will show. Click "Install certificate...". Figure 5-17 Install certificate Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 31 7. Select "local machine" option, then click "Next" button. Figure 5-18 Choose local machine location 8. Select "Place all certificates in following store" option and click "Browse..." button. Figure 5-19 Choose detailed stored location Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 32 9. In the file view, choose "Trusted Root Certification Authorities" folder and click "OK" button. Figure 5-20 Select certificate store 10."Trusted Root Certification Authorities" will show in the browse box. Click "Next". Figure 5-21 Certificate store selected Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 33 11.If the certificate is imported successfully, a message pop-up will show. Click "OK" to finish the process. Figure 5-22 Complete successful 12.Now you can restart the operator panel to apply the change. Figure 5-23 Restart HMI See also Changing account (Page 18) Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 34: Manual Login Mode

    Certificate error is displayed if the imported certificate does not match the certificate of the Control Unit: Setting selection When taping on this area, the connection setting window will appear: Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 35 You can change the language later in "Setting" screen page. Refer to the section entitled "Setting language (Page 37)". Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 36 If connecting to both CUs successfully, the following page appears for just 2 seconds, then the "Home" page shown in Section "Home" screen (Page 55) automatically opens. Figure 5-27 Connection established for CU1 Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 37 Figure 5-29 Connection established for dual circuits Note Same IP for two CUs is forbidden! Note The dual circuits feature for GH150 converters will be delivered soon. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 38: Automatic Login Mode

    Screen page "Settings" is used to set the basic operator panel settings. Admin access is required for setting in this page. Call screen page "Settings" by taping on Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 39: Setting Language

    Multiple languages can be selected in the HMI App setting. Users can set available languages according to the needs. 1. Tap on "Language". 2. Select the desired language from the ComboBox. Figure 5-32 Setting language Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 40: Setting Time Zone

    The time is synchronized with the Windows system time of the operator panel. Users can change panel time according to the needs. 1. Tap on "Timezone". 2. Select the corresponding time zone from the ComboBox. Figure 5-33 Settings time zone Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 41: Setting Control Unit Network

    IP. The IP address of the Control Unit can be changed successfully only if DHCP is deactivated. Figure 5-34 Settings network when single circuit under "Observer" account Network setting for single circuit Figure 5-35 Settings network when single circuit under "Administrator" account Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 42 The button "Apply settings" will be activated after a successful change of new IP in the input box. When taping it, a notice window will pop up. Figure 5-37 Notice Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 43: Setting The Password Of Different Accounts

    The dual circuit feature for GH150 air-cooled converters will be delivered soon. 5.5.5 Setting the password of different accounts Password setting requires Administrator right. Log in as Administrator before an attempt to change or assign password. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 44 • Make sure the entered password is different between "Actual password" and "New password" Although there is not strict limitation of password, Siemens strongly recommends that when setting up a new password, keep password complexity for your own security.
  • Page 45 • Make sure the entered password is the same between "New password" and "Confirm new password". Figure 5-42 Delete Observer password for single circuit Make sure inputting correct Observer password when you try to delete it. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 46: Enabling Remote Desktop On Operator Panel

    5.6 Enabling remote desktop on operator panel Enabling remote desktop on operator panel Remote desktop connection is enabled, bonded with default IP address in Siemens LDA factory. The IP address of X2P1 might vary depending on your configuration. If you want to change the IP address, keep in mind to set the RDP (Remote Desktop) firewall to only allow RDP traffic on X2P1.
  • Page 47 4. Remote Desktop (TCP-In) Figure 5-44 Firewall inbound rules 5. Go to the Properties->Scope tab, default IP address is shown in the IP address box. Figure 5-45 Default IP address Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 48: Ip Change

    Allow RDP for new IP address IP change Note When IP address is to be changed, new IP address for remote desktop should be enabled beforehand. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 49 IP address is set to 192.168.0.1 for CU1 connection and 192.168.0.2 for CU2 connection as Siemens LDA factory default. However, users may want to reset the IP address according to their own working environment. Use STARTER to reset the IP address.
  • Page 50 Operator panel configuration 5.7 IP change 3. Edit IP address in the pop-up window. Figure 5-49 Edit Ethernet node Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 51 6. After IP change, start HMI App, and there may be CU connection error. The certificate must be re-imported and new IP addresses must be updated for CU connection. Refer to the sections entitled "Import certificate" and "Manual login mode (Page 32)". Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 52 2. Select "Change adapter settings" on the left side panel. Figure 5-52 Change adapter settings 3. Select the adapter and right click, then select "Properties". Figure 5-53 Adapter properties Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 53 Operator panel configuration 5.7 IP change 4. Double click "Internet protocol version 4 (TCP/IPv4)". Figure 5-54 Internet protocol version 4 Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 54 5. Select "use the following IP address", and type IP address / subnet mask as actual need. Click OK button. Figure 5-55 Change IP address 6. Click OK again. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 55 After the IP change, set the RDP (Remote Desktop) firewall to only allow RDP traffic on X2P1, referring to Section "Enabling remote desktop on operator panel". Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 56 Operator panel configuration 5.7 IP change Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 57: Hmi App Screen Description

    Start the HMI app. The "Home" screen page is shown by default. You can also tap on call for the "Home" page. The screen page "Home" is divided into several areas. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 58 Display Home: motor running state, converter state, etc. Diagnostics: message; event Monitoring: status, cells, temperature, re-cooling Parameters: parameter list Settings: time zone, networks, user accounts Help Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 59 • Power Each indicator displays a real time value at the center of the gauge and a dial shows the percentage value based on the setpoint. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 60 "Diagnostics" page in Section "Diagnostic" screen (Page 61). When errors are addressed, tap on "Acknowledge" to enable the outstanding local control functions. Figure 6-4 Local control area Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 61 Acknowledge the value and the direction of rotation using one of the arrow keys. • Communication life-sign monitoring When clicking "Local" button, the following window will pop up to allow life-sign time setting. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 62 The default time is 6s. Users can choose default time by clicking "Set default". Anything confused, click "Safety notes" to get more information. Figure 6-6 Safety notes Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 63: Diagnostic" Screen

    Figure 6-7 "Message" screen Searching and filtering messages Users can search and filter the needed messages through following methods: • Input message keyword • Change time range Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 64 Order the messages Messages display is sorted by incoming by default. Users can reorder messages according to when they occurred by clicking the table header elements. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 65 Message sorting "Event" screen The "Event" screen displays the following information: • Event number • Event occurrence date and time • Event text Figure 6-11 "Event" screen Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 66: Monitoring" Screen

    "Date and time". Figure 6-13 Order the events "Monitoring" screen The "Monitoring" screen page displays the following information: • Status of control bits • Cell information • Cabinet temperature Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 67 The "Cells" screen page displays the following information: • Cell ID • Cell status Calling the screen 1. Tap in the navigation bar on 2. Tap on "Cells". Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 68 No status Green Charged Fault Yellow Alarm Blue Bypassed Reset cell status "Bypass" As administrator, you can reset the "Bypass" cell status when possible. 1. Tap on Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 69 Other GH150 Air-cooled converters may not have Air-Air Heat Exchanger Fans or have less number of fans on top of MoM. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 70: Parameters" Screen

    • Parameter number and text • Parameter value and unit Calling the screen 1. Tap in the navigation bar on Figure 6-18 "Parameters" screen under "Observer" account Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 71 5. Save the changes by tapping on "Save changes". If you change the parameter values but not clicking "Save changes", the new values can not be set to CU successfully after rebooting CU. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 72: Setting" Screen

    Using a QR scanner, users can directly access the home page of Technical Support. Calling the screen 1. Tap in the navigation bar on Figure 6-21 "Help" screen Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 73: Installation, Update, Backup And Recovery

    Start Rufus program. Select your USB stick in "Device" selection pulldown menu, and select the iso file downloaded from Pridanet in the "Boot selection" field. And the "File system" should be NTFS. Click "Start" button. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 74 Installation, update, backup and recovery 7.2 Image installation Figure 7-1 Start Rufus A warning message will pop up. Click "OK" to continue. Wait the process to complete. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 75 Installation, update, backup and recovery 7.2 Image installation Figure 7-2 Rufus warning The iso file is burned into the USB stick successfully. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 76 Installation, update, backup and recovery 7.2 Image installation Figure 7-3 Rufus process complete Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 77 ① "ESC" key ② "Enter" key ③ Arrow keys Figure 7-4 External keyboard 2. The BIOS menu will be shown. Select "Boot Manager". Figure 7-5 Main BIOS menu Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 78 As the standard windows deployment resolution is 800 x 600. During the installation process, you will not be able to see the upper part of the screen, but it will not matter during the installation process. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 79 Installation, update, backup and recovery 7.2 Image installation 5. Select "Install OneIPC Image" and click "Next" button. Figure 7-8 Install OneIPC Image 6. Click "Next" button directly. Figure 7-9 Change IPC name Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 80 7. Click "Next" button directly. No need to change any setting here. Figure 7-10 Set local time and keyboard 8. Click "Begin" to start the installation. Figure 7-11 Start installation Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 81 9. Installation process begins and your IPC will reboot twice automatically during the installation process. Figure 7-12 Installation process 10.Select language and time zone, and click Next. Figure 7-13 Basic information Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 82 11.Enter the product key, and click Next. If the IPC277E is not connecting to Internet, you can select "Do this later". Refer to Section "Windows activation (Page 91)". Figure 7-14 Enter product key 12.Click "Accept". Figure 7-15 Legal stuff Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 83 Installation, update, backup and recovery 7.2 Image installation 13.Click "Use Express setting". Figure 7-16 Get going fast Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 84 14.The IPC will reboot then. Once HMI app is shown, IPC is installed and ready to enable applocker automatically. Sometimes this process will take more then 60 minutes. Be patient to wait. Figure 7-17 Applocker enable process Figure 7-18 Applocker enabling Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 85 • Check your IP address is correct (X2P1). Default IP address is 192.168.0.10. • Make sure that the RDP is enabled for Agent Admin on that IP address, referring to Section "Enabling remote desktop on operator panel (Page 44)". Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 86: Agentadmin Password Change

    1. Search and click "Remote Desktop Connection" via search tool in "Start" menu. Figure 7-21 Start RDP 2. Click "Show Options" on the bottom left corner in th pop-up window. Figure 7-22 Show options Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 87 3. Enter IP address and username "AgentAdmin", then click "Connect" button. Figure 7-23 Connect Remote Desktop 4. Enter the given password for AgentAdmin account, referring to the section entitled "Password management". Figure 7-24 Enter given password Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 88 IPC, you must go to the IPC and click Yes on the IPC screen. Figure 7-26 Connecting Remote Desktop 7. Change the password as instructed as below. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 89 "Quit". Figure 7-27 Quick tapping Figure 7-28 Quit 2. Select the AgentAdmin account and login with the given password, referring to the section entitled "Password management". Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 90 Installation, update, backup and recovery 7.2 Image installation Figure 7-29 Switch to Agent Admin 3. Change your password as instructed as below. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 91 Start-Setting 2. Select "Accounts". Figure 7-31 Setting screen 3. Go to "Sign-in Options" tab and click "Change" under the title "Password" on the screen. Figure 7-32 Sign-in options Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 92 Installation, update, backup and recovery 7.2 Image installation 4. Enter the current password, then click "Next". Figure 7-33 Enter current password Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 93: Windows Activation

    If Microsoft Windows is not activated during the image installation process, you can activate Microsoft Windows later by two methods: online activation and phone all activation. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 94 (The product key can be found on the backside of the IPC). Then perform as the following: 1. Go to Setting screen via Start menu of the IPC. Figure 7-35 Start-Setting 2. Select "Update & Security". Figure 7-36 Setting screen Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 95 3. Go to "Activation" tab on the left and click "Change product key" in the right workspace. Figure 7-37 Activation tab 4. Enter the product key. Figure 7-38 Enter a product key 5. If you enter the correct product key, Windows is activated. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 96 Firstly login the IPC via remote desktop connection. Then perform as the following: 1. Type "slui 4" in search box of your remote desktop. Figure 7-39 slui 4 2. Select your country or region. Figure 7-40 Select country or region Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 97 4. The voice guidance gives back the confirmation ID, fill them into the boxes. Figure 7-42 Enter confirmation ID Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 98 6. Windows activation by phone call is done. Figure 7-44 Activation done After Windows activation, you can double check the activation status by following path: Control Panel > All Control Panel Items > System Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 99: Updating Hmi App

    Check Microsoft Windows status Updating HMI App HMI App undergoes continuous development. Siemens strongly recommends that HMI App updates are applied as soon as they are available. In order to update the HMI App, you will need the latest HMI installation file. Instrutions how to get the latest installation file can be obtained from Product Note published in LDA Portal (https://www.lda-portal.siemens.com/).
  • Page 100 2. Insert the USB stick and copy the installation file to IPC277E directly. Remove the USB stick. 3. Locate the Applocker folder short-cut on IPC277E desktop. Double click and open the Applocker folder. Figure 7-48 Applocker short-cut Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 101 4. Execute the script "010_disable_applicationcontrol" as Admin in order to activate service mode. Figure 7-49 Disable applicationcontrol 5. If the service mode is successfully activated, the following screen will show. Figure 7-50 Applocker disabled Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 102 Install new version 7. After the installation is finished, execute the script "020_Whitelisting" as Admin. It will take a little while, sometimes up to one hour. Figure 7-52 Whitelisting Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 103 Installation, update, backup and recovery 7.3 Updating HMI App 8. Press Enter key when it finishes. Figure 7-53 Whitelisting finished Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 104: Updating Windows

    Software update plays an important role for stable system operation. There are two types of Windows update for security patches: online update and offline update. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 105 Installation, update, backup and recovery 7.4 Updating Windows Online update Siemens recommends to update Windows online on SIMATIC IPC277E, proceed as follows: • Make sure the internet connection is established on SIMATIC IPC277E. • Open "Windows Update" in Settings. Figure 7-56 Windows Update...
  • Page 106 • Wait for updating. If error exists, the following screen will appear. If error can not be solved, then you can update Windows in offline method. Figure 7-58 Updating error Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 107 IPC Image version, and then go to Microsoft network to download the security patch. – Check your current Windows version or IPC Image version on SIMATIC IPC277E. Figure 7-59 Check Windows version Figure 7-60 Check IPC-Windows version Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 108 Click "Download" on the Windows 10 X64 based system patch. Figure 7-62 Search result and download selection Right click the mouse to select "Save link as..." to download the patch package to an USB stick. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 109: Backing Up And Recovery

    Prepare an external hard disk with 100 GB free storage at least and an USB stick with 8 GB free storage at least. External hard disk is used to save the backup system image and the USB stick is used to save the recovery drive. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 110 2. Click on "Create a recovery drive". A popup window will display. Do not select "Back up system files to the recovery drive". Click "Next". Figure 7-65 Create a recovery drive Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 111 Installation, update, backup and recovery 7.5 Backing up and recovery 3. Select the USB flash drive: F:\(RECOVERY). Click "Next". Figure 7-66 Select USB flash drive Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 112 4. Read the warning message. Click "Create" if your USB stick is ready. Figure 7-67 Warning for drive formatting 5. Recovery drive is ready. Click "Close". Figure 7-68 Recovery drive ready Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 113 SIMATIC IPC277E, click on "Backup and Restore (Windows 7)". Figure 7-69 Select backup and restore in control panel 2. Click on "Create a system image". Figure 7-70 Create a system image Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 114 4. "EFI System Partition" and "System (C:) (System)" are selected as default. Data (D:) is optional for backup. Click "Next". Figure 7-72 Select drive to include in the backup Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 115 Installation, update, backup and recovery 7.5 Backing up and recovery 5. Click "Start backup". Figure 7-73 Confirm backup setting 6. Backing up starts. Figure 7-74 Backing up files Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 116 7.5 Backing up and recovery 7. Click "No" to move on. Figure 7-75 Create a system repair disc 8. Click "Close" when the backup completes successfully. Figure 7-76 Backup successful Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 117 Figure 7-77 Settings 2. Select "Recovery" on the left side of the panel, and go to "Advanced startup" on the right section, click "Restart now". Figure 7-78 Recovery Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 118 3. In "Choose an option" screen, select "Use a device". Figure 7-79 Use a device 4. Select "EFI USB Device". The IPC will restart. Figure 7-80 EFI USB device Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 119 Installation, update, backup and recovery 7.5 Backing up and recovery 5. After restart, choose your keyboard layout. Choose "US" as example here. Figure 7-81 Choose keyboard layout 6. Select "Troubleshoot". Figure 7-82 Troubleshoot Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 120 7.5 Backing up and recovery 7. Select "System Image Recovery". Figure 7-83 System image recovery 8. Choose a target operating system, for example Windows 10. Figure 7-84 Choose target OS Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 121 9. Check "Select a system image" and click "Next". Figure 7-85 Select a system image 10.Select the hard disk that stores the system image backup. Figure 7-86 Select hard disk Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 122 7.5 Backing up and recovery 11.Select date and time of the system image to recover. Click "Next". Figure 7-87 Select date and time 12.Click "Next". Figure 7-88 Choose additional store options Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 123 Installation, update, backup and recovery 7.5 Backing up and recovery 13.Click finish. Figure 7-89 Re-image IPC 14.Click "Yes" to continue. Figure 7-90 Warning for re-image Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 124 7.5 Backing up and recovery 15.Wait the restoring until the process completes. Figure 7-91 Restoring 16.After restart, the device will display on the screen. Figure 7-92 HMI connection with CU Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 125: Password Management

    The passwords setup in HMI system includes: • AgentAdmin password • Web Administration password Two envelopes are delivered with the converters from Siemens factory to the customer. One is sealed, containing the initial password setup in the HMI system. The other envelope is open and empty.
  • Page 126 The second envelope will be handed over to the customer. Figure 8-3 Update passwords after commissioning Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 127 Customer can change the given passwords. In case changed passwords are forgotten: • Web Admin: reset the password by customers • AgentAdmin: contact Siemens customer service for reset Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 128 Password management 8.1 Password management Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 129: Service And Support

    You can find your local partner here (https://www.lda-portal.siemens.com/siemlda/en/contact/ form). Please have the following data ready: • Type (MLFB) • Serial number You can find this data on the rating plate. Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 130 Service and support Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 131: List Of Abbreviations/Acronyms

    Operating System Remote Desktop Protocol Shared Access Signature Secure Shell Transmission Control Protocol Trusted Platform Module User Interface Universal Serial Bus Virtual Machine VFD/Drive Variable Frequency Drive/Converter Web Based Management Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 132 List of abbreviations/acronyms B.1 List of abbreviations/acronyms Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 133: Index

    Technical support, 70 Header, 57 HMI program version, 70 website address, 70 whitelist, 11 Windows Defender, 11 Windows Security Center, 11 Local control, 58 Logging on to the "Observer" account, 21 Message, 61 Mointoring data, 57 Navigation bar, 56 Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...
  • Page 134 Index Operator panel for SINAMICS Perfect Harmony GH150 air-cooled MV Converters Function Manual, 12/2022, A5E51241343A...