Figure 3-163 Display Programming: Dns; Figure 3-164 Display Programming: Router Settings - Siemens GCP5000 Instruction & Installation Manual

Grade crossing predictor for electrified territory (gce)
Table of Contents

Advertisement

DISPLAY MODULE AND OFFICE CONFIGURATION EDITOR
_________________________________________________________________________________________________________
DNS
The DNS menu allows the user to set the IP address of name servers used for the domain
name system.

Figure 3-163 Display Programming: DNS

3.5.2.11.3
Router Settings
The Router Settings page is used when there is a CPU III in the system. This controls the
routing of vital ATCS messages from the CPU III when vital communication links are used.
When the parameter is set here, it is sent to the CPU III and then stored in the CIC, so that the
CPU III can read it on boot up, regardless of whether the Display module is present.
ATCS IP Field Interface has options of None, Echelon, and Ethernet, default Echelon. This
controls the routing of vital ATCS messages. If it is set to Echelon the CPU III will send vital
messages out of the Echelon port. If it is set to Ethernet, the CPU III will send vital messages
out of the CPU III laptop port.
ATCS IP Field UDP Port Number is the Ethernet port number used when the Field interface is
set to Ethernet. Default 13000.
The Route Table Entry timeout is used by the display module to delete ATCS route entries in
the route table if they are no longer used, range 0 -172800s, default 400s.

Figure 3-164 Display Programming: Router Settings

3-112
SIG-00-22-02
JUNE 2022 (Revised September 2022)
Version: B.1