DESCRIPTION Of THE TERMINALS
6.3.1.3 Temperature inputs
R1+
R1-
Figure 42:
Temperature inputs
NOTICE
6.3.1.4 Analog inputs
The analog inputs are optional.
AI0+, AI1+
I
AI0-,AI1-
Figure 43:
Analog inputs
6.3.1.5 Relay output
Figure 44:
Relay output
Terminals
X2A.10/12/14/16 R0+...R3+
X2A.9/11/13/15
U
Connection
two-wire
No potential separation !
The inputs are not electrically isolated from the control board, therefore
a motor temperature sensor must not be connected!
=>
„5.7.3 Motor temperature detection"
Terminals
X2A.6 / 8
X2A.5 / 7
Specification
U/I adjustable:
0...±10 V (Ri=55 kΩ)
0...±20 mA (Ri=250 Ω)
4...20 mA (Ri=250 Ω)
Terminals
X2A.1 / 2
RLA
Specification
U
: Max. 30 V / 0.01...1 A
dc
Max. number of switching cycles
10
mechanical; 500,000 at U
8
RLC
Others
Ohmic load only, or inductive load with suitable protective
circuit
Input type
Pt100
R0-...R3-
Measuring range
-40...+80 °C
Differential inputs
AI0+/AI1+
AI 0, AI 1
AI0-/AI1-
Resolution
11 Bit + sign
Output
RLA / RLC
: 30 V / 1 A
dc
63