CONNeCTION Of THe POWer UNIT

4.2.7 Connection of a temperature detection

4.2.7.1 Temperature detection terminals T1, T2

The COMBIVERT G6 is delivered with a PTC evaluation. The function corresponds to
EN 60947-8
function of T1, T2
PTC or
temperature switch
Figure 17:
Temperature detection terminals T1, T2

4.2.7.2 Terminal block X1C temperature detection

X1C
No.
1, 4
2
3
4
1
2, 3
5
Figure 18:
Terminal block X1C temperature detection
and works in accordance with the following table:
resistance
< 750 Ω
0.75...1.65 kΩ
(reset resistance)
1.65...4 kΩ
(tripping resistance)
> 4 kΩ
The behaviour of the drive controller in case of error/warning is defined with
parameter CP37 (Pn12). At factory setting the switching condition "9: dOH
warning" is set when terminals T1, T2 are open.
Name
function
T1, T2
Connection for temperature sensor
Insertion slots to release the cage
clamp terminal with screw driver
SD 0, 4x2.5 (DIN 5264)
5
Unlocking the terminal block
Display ru46
error/warning
T1-T2 closed
undefined
T1-T2 open
Cross-section
AWG with-
out wire-end
ferrule
24...16
stranded wire
mm² with
wire-end
ferrule
0.25...1
43