4.6 connection of a temperature detection
4.6.1 Temperature detection terminals T1, T2
The KEB COMBIVERT is delivered with a PTC evaluation. The function corresponds to
DIN EN 60947-8 and works in accordance with the following table:
function of T1, T2
PTC or
temperature switch
Figure 18:
Temperature detection
40
Resistance
< 750 Ω
0.75...1.65 kΩ
(reset resistance)
1.65...4 kΩ
(tripping resistance)
> 4 kΩ
The behaviour of the inverter in case of error/warning is defined with param-
eter CP37. As standard the PTC input is deactivated. An instruction for the
activation can be found in the annex.
Display ru46
Error/warning
T1-T2 closed
–
undefined
T1-T2 open
x