OVERLOAD fUNCTION

3.3 Overload function
Valid for drive controllers from firmware version 2.2.0.43.
The overload duration achievable in practice depends essentially on the cooling condi-
tions. The overload protection of the drive controller is triggered by the following causes:

3.3.1 AC-Motor (18 / 19 / 23P6)

3.3.1.1 Overload function (OL)

The OL function protects the drive controller against permanent overload. Depending on
the cooling, long-term operation in the overload range can lead to the "ERROR overheat
powermodules", which trips the drive before the OL function responds.
The following graphic shows the tripping time as a function of the respective constant
overload:
20
15
10
5
0
100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290
Figure 1:
Maximum tripping time depending on the overload for AC motors
Permissible heat sink temperature is exceeded, leading to the error message
"OH (Error overheat powermodules)".
Exceeding the tripping time leads to the error message "ERROR overload",
=>
„Figure 1: Maximum tripping time depending on the overload for AC
Motor current / drive controller rated current in %
18P6
19P6
motors".