DESCRIPTION Of THE TERMINALS

6.3.2 Control terminal block X2b

function
Name
Free
programmable,

digital inputs

Control release
Figure 45:
X2B pluggable terminal block with cage clamp terminals
6.3.2.1 Digital inputs
The digital inputs are specified in accordance with IEC61131-2 Type 3. All 24 V terminals
together are short circuit protected (250 mA).
24V
DI0...DI15
Figure 46:
Digital inputs
64
PIN
DI 15
32
DI 14
30
DI 13
28
DI 12
26
DI 11
24
DI 10
22
DI 9
20
DI 8
18
DI 7
16
DI 6
14
DI 5
12
DI 4
10
DI 3
8
DI 2
6
DI 1
4
DI 0
2
Terminals
X2B.2/4...32
X2B.1/3...31
PIN
Name function
31
24 V
29
24 V
27
24 V
25
24 V
23
24 V
21
24 V
19
24 V
17
24 V
24 V outputs to supply the
digital inputs
15
24 V
13
24 V
11
24 V
9
24 V
7
24 V
5
24 V
3
24 V
1
24 V
Input
DI0...15
DI 0...15
24V
Specification
Status „0": -3...5 V
Status „1": 11...30 V
: 4mA
I
in