4.2.4 Connection of the Output Supply Voltage

The supply voltage for the two output groups of 8 connections each can be
provided either internally using the supply voltage for the module, or exter-
nally from a separate power source. The base modules are provided with two
sets of terminal blocks in the middle row of the output terminals. The left-hand
terminal of each set carries the 24VDC module power, while the right-hand
terminal provides a connection point for the output supply voltage.
The base modules are shipped with jumpers installed in each of these termi-
nals, connecting 24VDC module power to connection point for the output
supply voltage.
Color
Fig. 4-10: Output supply voltage, internal
The factory-installed jumper has to be removed when a separate power supply
for a group of 8 digital outputs is required. The separately fused or switchable
power supply is connected to the right-hand connection point.
Color
Fig. 4-11: Output supply voltage, separate
Fieldbus Dependent I/O Module
CANopen
Outputs
grey
1
2
3
4
5
6
7
8
Supply of the output drivers
red
24 V
17 18
blue
33 34 35
36 37 38 39 40
Outputs
grey
Separate supply of the output drivers
1
2
3
4
5
6
7
8
for a group of 8 outputs
rot
24 V
17 18
blau
33 34 35 36 37 38 39 40
Jumper
0 V
No jumper to the supply of
the I/O module allowed!
0 V
Installation