Degree of Protection
Degree of protection according to
EN 60 529
Conformity and Certification
Conformity labelling
UL
Climatic Environmental Conditions
Operating temperature
Storage temperature
Relative air humidity
Air pressure in operation
Maximum altitude
Strain by harmful substances
Special conditions
Mechanical Strength
Vibration
Impact
Electrical Safety
Reverse voltage protection
Air and creepage distances
Isolation
Test voltage
Fieldbus Dependent I/O Module
CANopen
IP 20 protection against physical contact with
standard test probes
CE
E175199, UL 508
0 °C ... 55 °C
-25 °C ... +70 °C
10 ... 45 % , no dew formation
86 ... 106 hPa
max. 2000 m above sea level
Inspection according to IEC 60068-2-42 and
IEC 60068-2-43
Exercise caution when subjecting the I/O modules to
the following conditions:
– dust, corrosive vapors or gasses
– ionized radiation.
According to IEC 60068-2-6, inspection Fc
10 ... 57 Hz constant amplitude 0.075 mm
57 ... 150 Hz constant acceleration 1 g
According to IEC 60068- 2-27; 15 g, 11 ms
Yes
According to DIN EN 61131-2 and DIN EN 50178
between current circuits and body as well as between
electrically isolated, separate current circuits, accord-
ing to over-voltage category II, degree of pollution 2
Yes, between fieldbus and internal electronics
DC 500 V