WAGO CANopen 752 Manual page 12

Fieldbus dependent i/o module
Table of Contents

Advertisement

8 •
Technical Data
Wire connection
Power supply
Sensors, actuators
Supply voltage for
outputs (8 circuit group)
Inputs
Number of inputs
Input
Wire connection
Signal voltage (0)
Signal voltage (1)
Time constant
Insulation
electronics/field side
Outputs
Number of outputs
Rated voltage
Rated current
– max. per output
– max. per group (8 outputs)
– max. per module 16 DO
Leakage current
Short circuit protection
Max. operating frequency
(without bus)
– resistive load
– inductive load
Insulation
electronics/field side
Diagnosis
Feeding
®
CAGE CLAMP
0.08 mm² ... 2.5 mm², AWG 28-12*
®
CAGE CLAMP
0.08 mm² ... 1.5 mm², AWG 28-16
®
CAGE CLAMP
0.08 mm² ... 1.5 mm², AWG 28-16
* AWG12: THHN, TWHN
16
in accordance with EN 61131-2, type 1
for 3 conductors
DC –3 V ... +5 V
DC 15 V ... 30 V
5 ms
none
16
DC 24 V
500 mA
4 A
8 A
< 2 mA
electronic, automatic restart
1 kHz
utilization category DC 13, equals 6 Hz
none
Short circuit display by LED (OVERLOAD) for the
entire module; signalling via bus for 4 outputs each
all through supply terminal blocks 24 V, 0 V,
in groups via supply terminal blocks for 8 outputs
each
Fieldbus Dependent I/O Module
CANopen

Advertisement

Table of Contents
loading