16 •
Installation

4.2 Electrical Installation

4.2.1 General

ESD (Electrostatic Discharge)
The components are equipped with electronic components susceptible to be
destroyed when exposed to electrostatic load. Therefore, when handling these
components, ensure proper grounding of the surrounding objects and persons
(workplace, packing). Avoid contact with electrically conductive components,
e. g. the pins of a plug.
All connecting terminal blocks for the supply voltages and sensor and actuator
connections are equipped with CAGE CLAMP
These CAGE CLAMP
conductors. When using ferrules, select the next smaller nominal cross section
for the conductor.
CAGE CLAMP
Fig. 4-6: How to operate the CAGE CLAMP
The WAGO-I/O-SYSTEM 752 requires a 24 V DC supply.
The sensors supply voltage is short circuit protected by means of the plug-in
fuse F1 (TR 5 / 250 V / 6.3A T).
Note
Use UL-Recognized fuse only
The supply voltage for the outputs can be fed through the module, or sourced
separately. Rate the electrical fusing according to the technical data.
®