Output Assemblies (Drive Consumes) - YASKAWA 1000 Series Technical Manual

Ac drive
Hide thumbs Also See for 1000 Series:
Table of Contents

Advertisement

8

Output Assemblies (Drive Consumes)

The convention in this manual is from the PLC perspective. As such, an assembly is called an "Output Assembly" when
outputted from the PLC and received by this node. An "Input Assembly" is outputted from this node and read by the
PLC. This section details "Output Assemblies" that are "Consumed" by the drive.
Basic Speed Control Output - 20 (0x14)
Output Instance
Byte
20
Name
Run Fwd
Fault Reset
Speed Reference
Extended Speed Control Output - 21 (0x15)
Output Instance
Byte
21
Name
Run Fwd
Run Rev
Fault Reset
NetCtrl
NetRef
YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual
Bit 7
Bit 6
0
1
2
3
Forward Run Command
0: Stop
1: Forward Run
Fault Reset
0: No Fault Reset
1: Fault Reset
Speed Command
Sets drive speed reference
Speed reference data:
Frequency reference / 2
Setting range: 0 to 0xFFFF
For example, when setting a reference of 1024 with a speed scale of 2
Speed reference data = 1024 / 2
Unit depends on o1-03.
Bit 7
Bit 6
Net
0
Ref
1
2
3
Forward Run Command
0: Stop
1: Forward Run
Reverse Run Command
0: Stop
1: Reverse Run
Fault Reset
0: No Fault Reset
1: Fault Reset
Run command from Network
0: Depends on b1-02
1: Enables the run command from network
Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network
8 Output Assemblies (Drive Consumes)
Bit 5
Bit 4
-
Speed Reference (Low Byte)
Speed Reference (High Byte)
Description
SS
(SS: Speed scale)
= 256 = 0x0100
2
Bit 5
Bit 4
Net
Ctrl
Speed Reference (Low Byte)
Speed Reference (High Byte)
Description
Bit 3
Bit 2
Bit 1
Fault
Reset
Bit 3
Bit 2
Bit 1
Fault
Run
Reset
Rev
Bit 0
Run
Fwd
Bit 0
Run
Fwd
23