5.
Select the proper type and length of communication cables and drop line.
Refer to the ODVA website (www.odva.org) for more information on network cabling.
Refer to Trunk Line and Drop Line Length on page 78
Only connect network termination resistors (121 Ω, ±1%, 1/4 W) to nodes of the two ends of trunk line. Refer to
ODVA specifications for more details on DeviceNet termination.
6.
Prepare and connect the communication cables to the terminal block as shown in
particular precaution to ensure that each wire is properly connected and wire insulation is not accidentally
pinched into electrical terminals.
WARNING! Fire Hazard. Tighten all terminal screws according to the specified tightening torque. Loose electrical connections could
result in death or serious injury by fire due to overheating electrical connections. Tightening screws beyond the specified tightening
torque may result in erroneous operation, damage to the terminal block, or cause a fire.
NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not come into contact with other
wiring. Insufficient insulation may cause a short circuit that can damage the option or the drive.
Figure 8
Note: Separate communication cables from main circuit wiring and other electrical lines.
Figure 9
Preparing wire ends:
Pull back the shielding and lightly
twist the end with fingers, keeping
the ends from fraying.
YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual
Option terminal
Shield
Figure 8 Preparing Ends of Shielded Cable
about 5.5 mm (7/32")
When not using
crimped insulated
sleeves
Figure 9 Preparing and Connecting Communication Cable Wiring
for details on selecting trunk line and drop line lengths.
Insulation
DeviceNet Master
Shield
Shield sheath
(Insulate with electrical tape
or shrink tubing)
Screwdriver blade size
Blade depth of
0.4 mm or less
Blade width of
2.5 mm or less
Loosen the screws and
insert the wire into the
opening on the terminal block.
DeviceNet drop line
(do not solder ends)
5 Installation Procedure
Figure 8
and
Figure
Tightening torque:
0.5 to 0.6 N m
or 4.4 to 5.3 in-lbs
Terminal block CN1
9. Take