12 Troubleshooting
Drive Error
DeviceNet
Code
Error Code
(hex)
(hex)
<1>
1F
6320
20
0000
21
22
7500
23
24
25
8321
27
9000
<1> Drive error code is stored in MEMOBUS/Modbus address 0080 hex.
DeviceNet Option Fault Monitors U6-98 and U6-99
The DeviceNet Option SI-N3 can declare the error/warning conditions via drive monitor parameters as shown in
Table
22.
Fault Condition
No Fault
CPU Error
PLC in Idle State
Force Fault
Network Power Loss
Connection Time-out
Dup MAC ID
Bus-Off
Two drive monitor parameters, U6-98 (OPTN LATCH STAT) and U6-99 (OPTN ACTIVE STAT), assist the user in
network troubleshooting.
• U6-98 displays the first declared fault since the last fault reset or power cycle.
• U6-99 displays the present DeviceNet Option SI-N3 status.
These parameters are accessible from the DeviceNet network the or the drive digital operator. A drive fault reset or
power off clears and refreshes both U6-98 and U6-99.
Note: In the event of a PLC idle state, the action taken by the DeviceNet Option SI-N3 depends upon the value of parameter F6-54
(Idle Mode Fault Detection).
Automatic Device Replacement (ADR)
This DeviceNet Interface is compatible with the ADR feature associated with Rockwell controllers and DeviceNet
Scanners. ADR features Configuration Recovery and Auto Address Recovery.
Configuration Recovery (CR)
CR is the ability of the scanner to download previously uploaded and saved configuration data to the DeviceNet node.
When a DeviceNet node is removed and returned to the network or replaced with another device, an ADR-enabled
scanner reads the Electronic Key of the device that is configured in the scanner. A typical setup of the Electronic Key is:
Vendor ID, Product Code, Model Number and Product Revision. When the CR feature is enabled, the stored
configuration is downloaded to the DeviceNet node.
76
Description
EEPROM R/W Error (Err)
None
DeviceNet Comm Error (bUS)
Out of Control (CF)
External Fault 0 (EF0)
Table 22 DeviceNet Option Fault Monitor Descriptions
Status Value (U6-99/
Fault Declared
U6-98)
n/a
EF0
EF0
EF0
BUS ERROR
BUS ERROR
BUS ERROR
BUS ERROR
Cycle drive power – Replace drive if fault continues
Check DeviceNet network cable connections.
Check 24VDC power supply voltage.
Check DeviceNet Option Card installation and connections.
Cycle drive power – Replace DeviceNet Option or drive if fault continues.
Check motor parameters
Auto-tune
Check PLC program
Check MI switch setting
Check DeviceNet Option Card LEDs for fault indication
0
No faults.
1
Option board failure.
2
PLC is sending polled I/O with all data set to zero.
3
Network sent a message to force this node to the fault state.
1000
Power on DeviceNet network is off.
1001
This nodes timer (Expect Packet Rate) timed out.
This node and at least one other node have the same MAC ID.
1002
Another node sent its MAC ID to the network first.
1003
CAN transceiver senses network error.
YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual