Name
Fault Reset
NetCtrl
NetRef
Speed Reference
Torque Reference/Torque Limit
MEMOBUS/Modbus Message Command
(Vendor Specific Yaskawa Electric (YE) Assy) - 100 (0x64)
Output Instance
Byte
100
Note: This is a paired assembly (100/150).
Name
Function Code
Register Number
Register Data
Function Code
Note: Refer to the MEMOBUS/Modbus Data Table in the drive Technical Manual for a list of monitor data using the MEMOBUS/
Modbus message area.
YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual
Fault Reset
0: No Fault Reset
1: Fault Reset
Run command from Network
0: Depends on b1-02
1: Enables the run command from network
Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network
Speed Command
Sets drive speed reference
Speed reference data:
Frequency reference × 2
Setting range: 0 to 0xFFFF
For example, when setting a reference of 1024 with a speed scale of 2
Speed reference data = 1024 × 2
Unit depends on o1-03.
Torque Reference/Torque Limit
Sets the torque reference and torque limit in units of 0.1%.
Sets the torque reference when using torque control (d5-01 = 1).
Sets the torque limit when using speed control (d5-01 = 0).
The torque reference and torque limit are disabled when F6-06 = 0.
Bit 7
Bit 6
0
1
2
3
4
MEMOBUS/Modbus Function Code
Refer to Function Code Decode Table on page
MEMOBUS/Modbus Register Number
MEMOBUS/Modbus Register Data
Table 8 Function Code Decode Table
0x00
0x03
0x10
8 Output Assemblies (Drive Consumes)
Description
SS
(SS: Speed scale)
2
= 4096 = 0x1000
Bit 5
Bit 4
Function Code
Register Number (High Byte)
Register Number (Low Byte)
Register Data (High Byte)
Register Data (Low Byte)
Description
25.
MEMOBUS/Modbus Function
Bit 3
Bit 2
Bit 1
No Operation
Read Register
Write Register
Bit 0
25