YASKAWA 1000 Series Technical Manual page 26

Ac drive
Hide thumbs Also See for 1000 Series:
Table of Contents

Advertisement

8 Output Assemblies (Drive Consumes)
Standard Control (Vendor Specific Yaskawa Electric (YE) Assy) - 101 (0x65)
Output
Byte
Instance
0
1
Photocoupler 2
101
2
3
4
5
6
7
Output Instance
Run Fwd
Run Rev
Multi-Function Input 3
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
Multi-Function Input 7
Multi-Function Input 8
External Fault
Fault Reset
Multi-Function Digital Output
Multi-Function Photocoupler 1
Multi-Function Photocoupler 2
26
Bit 7
Bit 6
Multi-
Multi-
Function Input
Function Input
8
7
Multi-
Multi-
Function
Function
Photocoupler 1
Forward Run Command
0: Stop
1: Forward Run
Reverse Run Command
0: Stop
1: Reverse Run
Terminal S3 Function Input
0: Terminal S3 Function (H1-03) OFF
1: Terminal S3 Function (H1-03) ON
Terminal S4 Function Input
0: Terminal S4 Function (H1-04) OFF
1: Terminal S4 Function (H1-04) ON
Terminal S5 Function Input
0: Terminal S5 Function (H1-05) OFF
1: Terminal S5 Function (H1-05) ON
Terminal S6 Function Input
0: Terminal S6 Function (H1-06) OFF
1: Terminal S6 Function (H1-06) ON
Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON
Terminal S8 Function Input
0: Terminal S8 Function (H1-08) OFF
1: Terminal S8 Function (H1-08) ON
External Fault EF0
0: No External Fault (EF0)
1: External Fault (EF0)
Fault Reset
0: No Fault Reset
1: Fault Reset
Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F.
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-03 is set to F.
Bit 5
Bit 4
Multi-
Multi-
Function Input
Function Input
6
5
Multi-
Function
Digital Output
Speed Reference (Low Byte)
Speed Reference (High Byte)
Torque Reference/Torque Limit (Low Byte)
Torque Reference/Torque Limit (High Byte)
Torque Compensation (Low Byte)
Torque Compensation (High Byte)
YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual
Bit 3
Bit 2
Multi-
Multi-
Function Input
Function Input
4
3
Byte
Bit 1
Bit 0
Run
Run
Rev
Fwd
Fault
External
Reset
Fault

Advertisement

Table of Contents
loading

This manual is also suitable for:

Si-n3

Table of Contents