YASKAWA 1000 Series Technical Manual page 67

Ac drive
Hide thumbs Also See for 1000 Series:
Table of Contents

Advertisement

Instance
Attribute
ID
1
3
Motor Type
1
6
Rated Current [0.1 A]
1
7
Rated Voltage [1 V]
Control Supervisor Object - 41 (Class 0x29)
Services Supported
Service Code No. (hex)
Attributes Supported
Instance
Attribute
ID
0
1
Object Software Revision
Run 1 (Forward Run
1
3
Command)
Run 2 (Reverse Run
1
4
Command)
1
5
NetCtrl (Command)
1
6
State
1
7
Running 1 (FWD)
1
8
Running 1 (REV)
1
9
Ready
1
10
Fault
YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual
Name
Displays the type of motor used.
3: PM motor
7: IM motor
Determined by the control mode set
to A1-02.
When A1-02 = 5, 6, 7, this attribute
becomes 3 (PM motor).
When A1-02 = 0, 1, 2, 3, this attribute
becomes 7 (IM motor).
Motor rated current.
Displayed in 0.1 A units. Changes
according to the current scale (CS).
Motor rated voltage.
Displayed in 1 V units. Changes
according to the voltage scale (VS).
0E
10
05
Name
Revision number of the Control
Supervisor Object.
Forward Running
0: Stop
1: Forward Running
Reverse Running
0: Stop
1: Reverse Running
Run command from Network
0: Depends on b1-02
1: Enables the run command from
network
Drive status.
2: Not ready
3: Ready (stopped)
4: Enabled (Run command present)
5: Deceleration to stop
6: Fault stop
7: Fault
Forward Running
0: Stop
1: Forward Running
Reverse Running
0: Stop
1: Reverse Running
Drive Ready
0: Not ready
1: Ready
Drive Fault
0: No Drive Fault
1: Fault
Description
Get
Description
10 General Class Objects
Set
Size
Range
Byte
Byte
Byte
Service Name
Get Attribute Single
Set Attribute Single
Reset
Get Set
Size
Range
Word
Byte
0, 1
Byte
0, 1
Byte
0, 1
Byte
Byte
Byte
Byte
Byte
Default
Depends on A1-02,
Control Method
Selection
Depends on capacity
Depends on capacity
Default
1
0
0
0
3
0
0
1
0
67

Advertisement

Table of Contents
loading

This manual is also suitable for:

Si-n3

Table of Contents