Error Code
Option generated busy event. The MEMOBUS/Modbus requested operation is in the process loop but the drive is not done yet.
Writing "Enter" when drive is running.
0x22
Attempt to write data that is read only.
Attempt to write a constant when drive is running.
During a CPF06 event attempting to write to registers other than A1-00 to A1-05, E1-03, o2-04.
0x23
Attempting to write during a drive undervoltage (Uv) event.
0x24
Attempting to write while the drive is storing data.
Change of State Response (Vendor Specific Yaskawa Electric (YE) Assy) - 199
(0xC7)
Input Instance Byte
0
1
2
199
3
4
5
6
7
Parameter
Run Fwd
Run Rev
External Fault
Fault Reset
NetRef
NetCtrl
Multi-Function Input 3
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual
Bit 7
Bit 6
Multi-
Multi-Function
Function
Input 3
Input 4
FAULT
ALARM
NetCtrl
NetRef
(Status)
(Status)
Forward Run command from Network
0: Forward Run command is not from network
1: Forward Run command is from network
Reverse Run command from Network
0: Reverse Run command is not from network
1: Reverse Run command is from network
External Fault command from Network
0: External Fault command is not from network
1: External Fault command is from network
Fault Reset command from Network
0: Fault Reset command is not from network
1: Fault Reset command is from network
Reference command from Network
0: Reference command is not from network
1: Reference command is from network
Run command from Network
0: Run command is not from network
1: Run command is from network
Terminal S3 command by Network
0: Terminal S3 command OFF
1: Terminal S3 command ON
Terminal S4 command by Network
0: Terminal S4 command OFF
1: Terminal S4 command ON
Terminal S5 command by Network
0: Terminal S5 command OFF
1: Terminal S5 command ON
Terminal S6 command by Network
0: Terminal S6 command OFF
1: Terminal S6 command ON
Description
Bit 5
Bit 4
NetCtrl
NetRef
Fault Reset
READY
Speed Agree
Output Frequency (Low Byte)
Output Frequency (High Byte)
Actual Torque (Low Byte)
Actual Torque (High Byte)
Data
9 Input Assemblies (Drive Produces)
Bit 3
Bit 2
External
Run Rev
Fault
Multi-
Multi-
Function
Function
Function
Input 8
Input 7
Input 6
REV
Reset
Running
2nd Motor
Bit 1
Bit 0
Run Fwd
Multi-
Multi-
Function
Input 5
ZSP
Running
Uv
oPE
59