8. Use the insert-eject lever to fully seat and automatically lock the board into
position.
The usual failure of the service LED to transition from on to off within 60 seconds
after insertion, indicating a power-status control fault, does not apply for the CPU
board.
9. Verify the LED status per
10. Review the platform message log to verify SMS has received the message that the
component has been inserted, by typing:
sc% showlogs -F
Review the board insertion message. You will see a message similar to the one
below.
Jun 16 14:30:05 2003 sun15-sc0: esmd[7167]: [0 4824421445907014
NOTICE Boards.cc 1646] CPU at SBxx inserted
where xx is the CPU assembly 0-17.
11. Close the Sun Fire E25K/E20K system cabinet access doors.
8.2.5

Verifying a CPU (Slot 0) Board

1. Using dynamic reconfiguration, configure the CPU board into the domain(s) by
using the Sun Management Center or by typing the following SMS command:
sc% addboard -d domain_id SBx
where x is the CPU Board 0-17.
domain_id is the letter A-R of the target domain(s) for the component.
OR
If the domain was shut down prior to the expander replacement, start the domain
by typing:
sc% setkeyswitch -d domain_id
8-8
Sun Fire E25K/E20K Systems Service Manual • April 2004
.