Powering Off The System For Sun Fireplane Interconnect Replacement - Sun Microsystems Sun Fire E25K Service Manual

Hide thumbs Also See for Sun Fire E25K:
Table of Contents

Advertisement

13.3
Powering Off the System for Sun
Fireplane Interconnect Replacement
Caution – The Sun Fireplane interconnect is NOT a hot-swappable component. This
procedure requires a complete shutdown of the domains and SCs, and disconnection
of all AC power to the system.
1. As a superuser on the domains, systematically shut down all running domains
by typing:
domain_name# shutdown -y -g seconds -i 0
where seconds is the amount of time before shutdown.
2. On the main SC, power off the domain hardware by typing:
sc% poweroff
This command powers off the entire system with the exception of the power
supplies, fans, and the SCs. Refer to poweroff(1M) for more information.
3. Shut down the System Control boards by doing the following:
As a superuser on the spare SC, shut down the spare SC by typing:
I
sc_spare# shutdown -y -g seconds -i 0
where seconds is the amount of time before shutdown.
On the main SC, power off the spare SC by typing:
I
sc% poweroff SCx
where x is 0 or 1, dependent upon which SC is the spare.
13-4
Sun Fire E25K/E20K Systems Service Manual • April 2004

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sun fire e20k

Table of Contents