7. Review the platform message log to verify SMS has received the message that the
component has been inserted, by typing:
sc% showlogs -F
Review the board insertion message. You will see a message similar to the one
below.
Jun 16 14:30:05 2003 sun15-sc0: esmd[7167]: [0 4824421445907014
NOTICE Boards.cc 1646] HPCI at IOxx inserted
where xx is the hsPCI+ assembly 0-17.
8. Close the Sun Fire E25K/E20K system cabinet access doors.
9.1.2.5
Powering On an hsPCI+ (Slot 1) Assembly
G
Power on the hsPCI+ Assembly by using the Sun Management Center or by
typing the following SMS command:
sc% poweron IOx
where x is the hsPCI+ Assembly 0-17.
9.1.2.6
Verifying an hsPCI+ (Slot 1) Assembly
1. Using dynamic reconfiguration, configure the hsPCI+ Assembly into the domain
by using the Sun Management Center or by typing the following SMS command:
sc% addboard -d domain_id IOx
where x is the hsPCI+ Assembly 0-17.
domain_id is the letter A-R of the target domain(s) for the board.
OR
Chapter 9 I/O (Slot 1) Assemblies
9-7