R&S NGE-K101 User Manual page 86

Table of Contents

Advertisement

www.allice.de
®
R&S
NGE100B
User Manual 5601.1343.02 ─ 02
Return values:
<arg0>
ON
Fuse is tripped.
OFF
Fuse is not tripped.
Example:
INST OUT1
FUSE:TRIP? -> 0
Fuse of Ch 1 has not tripped.
Usage:
Query only
FUSE:UNLink <arg0>
This command unlinks the channel fuses (fuse linking) for the previous selected chan-
nel.
Parameters:
<arg0>
{1 | 2 | 3}
1
channel Ch 1
2
channel Ch 2
3
channel Ch 3
Example:
INST OUT1
FUSE:LINK 2
FUSE:UNL 2
Fuse Ch 1 is unlinked with Ch 2
Usage:
Setting only
FUSE[:STATe] <arg0>
This command defines or queries the fuse for the previous selected channel.
Parameters:
<arg0>
{0 | 1}
1
Fuse will be activated.
0
Fuse will be deactivated.
*RST:
Example:
INST OUT1
FUSE ON
Fuse of Ch 1 is activated
FUSE? -> 1
Return fuse state of the selected channel.
Allice Messtechnik GmbH
Remote Control - Commands
OFF | 0
Remote Control
84

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nge102bNge103bNge100bNge-k102Nge-k103

Table of Contents