Commissioning
106
9.5.8
Configuration of the limit evaluation
A limit evaluation can be configured for up to 4 tank variables. The limit evaluation issues
an alarm if the value exceeds an upper limit or falls below a lower limit, respectively. The
limit values can be defined by the user.
A
1
2
3
4
5
6
7
8
52
Principle of the limit evaluation
A
Alarm mode = On
B
Alarm mode = Latching
1
HH alarm value
2
H alarm value
3
L alarm value
4
LL alarm value
5
HH alarm
6
H alarm
7
L alarm
8
LL alarm
9
Clear alarm = Yes
10
Hysteresis
The limit evaluation is configured in the Alarm 1 to 4 submenus.
Navigation path: Setup → Advanced setup → Alarm → Alarm 1 to 4
10
Proservo NMS83
B
10
1
2
3
4
5
6
7
8
Endress+Hauser
9
A0029539
Need help?
Do you have a question about the Proservo NMS83 and is the answer not in the manual?