Proservo NMS83
HTMS mode
Navigation
Description
Selection
Factory setting
Additional information
Manual density
Navigation
Description
Endress+Hauser
1
2
74
HTMS hysteresis
1
Value calculated
2
Value held/manual
L
Minimum level (→ 264)
min
H
Hysteresis (→ 265)
r
Description of parameters
Navigation
Setup → Advanced setup → Application → Tank calculation
Setup → Advanced setup → Application → Tank calculation → HTMS → HTMS mode
Defines the HTMS mode. Depending on the mode one or two pressure transmitters are
used.
• HTMS P1
• HTMS P1+P3
HTMS P1
Read access
Write access
Meaning of the options
• HTMS P1
Only a bottom pressure transmitter (P1) is used.
• HTMS P1+P3
A bottom (P1) and top (P3) pressure transmitter are used. This option should be selected
for pressurized tanks.
Setup → Advanced setup → Application → Tank calculation → HTMS → Manual
density
Enter the manual density value.
→ HTMS
Operator
Maintenance
Operating menu
Hr
Lmin
A0029148
263