Fuel Dispensers TATSUNO EUROPE ‐ Installation and User Manual , revision 10, January 2022
Picture 71 ‐ Spatial restrictions for AdBlue dispensers without ATEX certification
Legend: 1‐ Top view (without scale), 2‐ Front view (no scale), 3 Prohibited area (dispensers without ATEX certification must not be installed in
this area), E‐ Fuel dispenser hose reach, H‐Height of dangerous zone.
3.3.3. ORIENTATION OF A SINGLE‐SIDED DISPENSER
Single‐sided dispenser stands are labelled "L" and "R" ("L" left/left‐sided and "R" right/right‐sided) after the
dispenser type designation, e.g., BMP4011.OWL, see section 2.4. Dispenser orientation is determined by a view
of the dispenser from the vehicle arrival direction, see Figure 1.
3.3.4. DISPENSER DISTANCE FROM A TANK–FUEL TANK
The manufacturer recommends that the maximum distance of dispensers from storage tanks (gasoline, diesel,
LPG, WSE and AdBlue®) should be 50 meters and the suction height up to 5.5 meters. Under other conditions,
the suction capacity of dispensers equipped with pumps may be impaired, resulting in a reduction in pumping
performance (rated flow) or an increase in the noise level of the dispenser. All technological requirements for
the fuel station must be solved in a professionally designed and approved fuel station project consulted with
the dispenser manufacturer.
3.3.5. LIQUID FUEL TANK TYPE
Dispensers for pumping liquid fuels and technical liquids (diesel, gasoline, AdBlue, WSE...) can be connected to
both underground and over ground storage tanks.
95