Security Line (Stop Button); Regulation Of Valves In Pressure Sections Outside Dispenser (Cng Module) - tatsuno OCEAN TOWER Series Installation And User Manual

Table of Contents

Advertisement

Fuel Dispensers TATSUNO EUROPE ‐ Installation and User Manual  ,  revision 10, January 2022 
a.s. about the necessity to install service lines. For service lines we recommend using multi‐wire shielded 
H05VVC4V5‐K cables (0.5 mm
3.5.6. SECURITY LINE (STOP BUTTON) 
The security line serves to output the signal from the STOP button located in the dispenser to the station 
switchboard  security  circuits.  The  security  line  must  be  especially  installed  in  LPG  and  CNG 
dispensers/modules  that  operate  in  an  unattended  mode.  Pressing  the  STOP  button  on  the  dispenser 
activates the security circuits that disconnect the dispenser from the power supply and at the same time 
the safety valves on the supply line close. 
In order to install the security line it is necessary to route the 3‐wire power cable H05VV5‐F 3x1.5 (see 
Table 22) to each dispenser at the fuel station. The security line cable is always brought from the main 
switchboard  in  the  booth  to  the  first  module  of  the  dispenser  into  the  distribution  box.  From  the 
distribution box, the cable is routed to the dispenser electronic head where it is connected to the STOP 
button. 
 
3.5.7. REGULATION OF VALVES IN PRESSURE SECTIONS OUTSIDE DISPENSER (CNG MODULE) 
If the valves from high‐pressure sections are located at the CNG fuel station outside the dispenser in the 
area of pressure reservoirs and compressor then their switching is performed by a 5‐wire H05VV5‐F 5G1.5 
cable (see Table 14). The cable from valves regulation is routed from the main switchboard in the booth 
to the supply distribution box of the dispenser. The H05VV5‐F 5G1.5 cable is routed from the distribution 
box to the counter case to the outputs that ensure the valves regulation. 
Table 23 – Identification of wires in the cable for regulating the valves in CNG pressure sections 
 
 
CAUTION
 
In order to regulate external valves the dispenser outlets are used that use the voltage of 24V DC 
with maximum current‐carrying capacity of 0.8 A for switching. Always consult the dispenser manufacturer for 
the use of another control voltage and current. 
2
). 
Table 22 – Identification of wires in the security line 
Identification of wires in the H05VV5‐F 3x1.5 cable 
identification 
colour 
ST 
black2 
ST 
black1 
PE 
yellow‐green 
Identification of wires in the H05VV5‐F 5x1.5 cable 
identification 
colour 
V1 
black 1 
V2 
black 2 
V3 
black 3 
VC 
black 4 
PE 
yellow‐green 
description 
STOP signal 
STOP signal 
protection wire 
description 
valve 1 regulation 
valve 2 regulation 
valve 3 regulation 
common wire for valves 
protection wire 