Fuel Dispensers TATSUNO EUROPE ‐ Installation and User Manual , revision 10, January 2022
5.3.14. DISPENSER OPERATION TERMINATION
RECOMMENDATION
Switch off the 3x400 V the power supply circuit breaker for electric motors of pumps and vacuum pumps.
Switch off the 230 V circuit breaker for stabilized power supply of the electronic counter of the dispenser.
Switch off the backup UPS located in the booth by a switch located at the rear panel (the green LED on the UPS turns
off).
After switching off the power supply of the electronics in the
fuel station switchboard, the "OFF" message is displayed on
the unit price display and the display illumination switches off.
The last data is shows on the display for at least 15 minutes
after the power supply disconnection. After elapsing this
period and "erasing" the display the display status is saved into
the counter memory and will be shown after the power supply
is connected again – see the previous section.
Now the dispenser is out of order.
The manufacturer recommends disabling the dispenser in the following order:
153
€
406.1
L
15.326
€/L
OFF