Fuel Dispensers TATSUNO EUROPE ‐ Installation and User Manual  ,  revision 10, January 2022 
5. OPERATION 
5.1. INSTRUCTIONS FOR SAFE OPERATION 
Dispensers are complex devices that have to secure a whole range of difficult functions. Therefore, cleaning of 
the storage tanks, piping systems and inspection of the pumped medium cleanliness must be carried out before 
commissioning.  An  inspection  of  wiring  and  a  check  of  connection  correctness  must  be  performed  before 
commissioning in order to prevent any electric shock injuries and to ensure safety against explosion. 
Smoking forbidden 
 
NOTICE‐>LPG  
For LPG dispensers/modules, a pressure test of the LPG dispenser must be performed with a pipeline 
system by pressure of 2.5 MPa, including a review, before commissioning.
 
NOTICE‐>ADBLUE 
 
AdBlue®  dispensers/modules  must  be  pressurized  at  0.35  MPa  before  commissioning  the 
AdBlue® dispenser together with the piping system in order to perform a pressure test.
 
WARNING
Dispensers are hygienically harmless for the customer and operator. It is advisable to protect your hands, 
for example, with eco‐friendly gloves during normal maintenance and during deliveries. In case of skin contact, wash 
the affected area as soon as possible with soap and water. In case of eye contact, etc., seek medical attention. During 
deliveries, avoid inhalation of vapours of the pumped medium.
 
CAUTION 
It is forbidden to smoke and use open fire in the immediate vicinity of the dispenser.  
The smoking ban applies also to passengers inside the vehicle. 
It is forbidden to use mobile phones in the immediate vicinity of the dispenser. 
It is forbidden to pump into the vehicle tank while the engine is running.
 
CAUTION‐>LPG 
Technical and technological devices must correspond to approved conditions together with regulations for 
safe operation and maintenance as well as solutions of emergencies. The device must be fitted with carbon‐
dioxide extinguishers according to the fire‐safety solution. 
The LPG fuel station may only be operated by demonstrably trained persons. 
The "STOP button" is placed at the dispenser (for emergency situations). The procedure in case of fire or 
emergency  is  precisely  defined  in  local  operating  rules  and  regulations  –  the  attendant  must  be 
demonstrably trained with regard to this. 
The "STOP line" must be located at least 5 meters from the dispenser. 
LPG containers, piping and dispenser must be earthed, the grounding point for the pumping tank must be 
established and marked. 
 
Open flame use  
 
forbidden 
 
131
 
Use of mobile phones forbidden 
 
 
 