In order to install the data line, it is necessary to route the 4‐wire shielded H05VVC4V5‐K 5x0.5
communication cable (see Table 20) to each dispenser at the fuel station. The data cable must be routed
radially from the station control (booth, control panel) to the first module of each dispenser into the
communication distribution box. From the communication distribution box, the data line is led to the
dispenser electronic head of the dispenser and connected to the counter.
NOTICE
For the communication line, we recommend using a 5‐wire shielded communication cable with a
minimum wire cross‐section of 0.5 mm
gasoline vapour. For this purpose, the manufacturer recommends using H05VVC4V5‐K harmonized cables.
The TATSUNO EUROPE dispensers are standardly equipped with a PDE data line which is the RS485 line
with the PDE communication protocol. However, it is possible on customer's demand to add a data
converter to the dispenser counter which will concert the PDE data line to a line of another type and
communication protocol, e.g. PUMA LAN, ER4, IFSF‐LON, TATSUNO Party Line, etc. This also changes the
meaning of wires in the data cable. Identification of wires for the most used types of data lines is described
below, see Table 21.
Identification of wires in the H05VVC4V5‐K 5x0.5 cable for different types of data lines
wire colour
PDE
shield
ST
black 5
reserve
black 4
reserve
black 3
reserve
black 2
B
black 1
A
NOTE
For some type of data line a 2‐wire or 3‐wire cable would be sufficient ‐ see Table 21. Since the data line
type may change during operation depending on the used control system, we recommend using a 5‐wire cable.
3.5.5. SERVICE LINES
Service lines serve for special purposes. These lines are not necessary for the immediate dispenser
operation but they are also used in cases when it is necessary to remotely control some of the dispenser
functions or lead some signals out of the dispenser. Always consult the engineers of TATSUNO EUROPE,
Table 20 – Identification of wires in the data line
Identification of wires in the H05VVC4V5‐K 5G0.5 cable
identification
colour
SH
shield
‐
black5
‐
black4
‐
black3
B
black2
A
black1
2
. The jacket of the cable must be self‐extinguishing and resistant to
Table 21 – Identification of wires for different types of data lines
Easy Call
PUMA LAN
ST
ST
reserve
unused
reserve
0V
0V
AM
D(+)
RX
D(‐)
TX
TATSUNO EUROPE a.s., www.tatsuno‐europe.com
description
shield
reserve
reserve
reserve
data B
data A
PUMA LAN
ER4
+ probes
ST
ST
LL1
reserve
LL0
ZB
GND
YB
RX
ZA
TX
YA
106
DART
ST
reserve
reserve
reserve
B
A
ACTL
ST
reserve
Rx‐
Rx+
Tx‐
Tx+