Installation manual
If you obtain the "AAX0001 Com GSM/GPRS + RS-485" board after having the Ingecon
munication via standard RS-485, install the new board. To do this, the "AAP0022 Com RS-485" board of the first
module must be replaced with the "AAX0001 Com GSM/GPRS + RS-485" board. Observe the precautions stipulated
in section "4.3.2. Additional risks and measures in handling tasks" for Handling tasks (page 28).
Once mounted on the board, the communication RS-485 cables must be wired as they were on the other board, and
the rod must be connected as described above.
Connect the rod cable to the cable's rod output, and feed it out through the holes on the upper left side of the enclo-
sure. Connect the end that goes outside to the rod and attach it via its magnet to the unit's enclosure.
See "AAX2002IKH01 Installation Guide for Communications Devices".

5.4.8. Connection for ethernet communication

At the request of the installer, inverters may optionally incorporate hardware for communicating via ethernet. This
hardware comprises one to three "AAP0022 Com RS-485" boards (one per module except for module 1) that are sup-
plied mounted on the control board in each power block, a "AAX0004 Com Ethernet + RS-485" board (for module
1), the communications terminal strip and the wiring between boards and terminal strip.
The unit is provided with a 211 Ohm ferrite rod. The cable connecting the "AAX0004 Com Ethernet
+ RS-485" board of the terminal (RS-485 output) must be inserted as close as possible to the
board, turning it around the centre hole twice.
The board is provided assembled on the control board and a bag (attached with a plastic tie) containing the Ethernet
cable. Connect the cable to the board's Ethernet output and feed it out through the holes on the upper left side of
the enclosure.
If you obtain the "AAX0004 Com Ethernet + RS-485" board after having the Ingecon
munication via standard RS-485, install the new board. To do this, the "AAP0022 Com RS-485" board of the first
module must be replaced with the "AAX0001 Com GSM/GPRS + RS-485" board. Observe the precautions stipulated
in section 4 for Handling tasks.
Once mounted on the board, the communication RS-485 cables must be wired as they were on the other board, and
the rod must be connected as described above.
See "AAX2002IKH01 Installation Guide for Communications Devices".

5.4.9. Connection for fibre optic communication

At the request of the installer, inverters may optionally incorporate hardware for communicating via fibre optic cable.
This hardware comprises one to four "AAP0009 Com Fibra" boards (one per module except module 1) that are sup-
plied mounted on the control board in each power block, a +5/10 W power supply and wiring between the blocks
(AQL0019 units).
The boards are supplied fully assembled, connected by fibre optic cables and fed from the power source located in
the first power module. The cable connecting the unit to the outside will have to be connected to the fibre optic cable
connecter closest to the power feed for module 1.
See "AAX2002IKH01 Installation Guide for Communications Devices".

5.4.10. Ground Connections

The metal parts of the inverter (equipment ground) are electrically connected to the earthing bar on the front of each
cubicle containing the the electronics of the equipment.
To ensure the safety of personnel, this terminal must be connected to the installation's ground.
AAV2000IKI01