5.3.4 Multipurpose inlets

cumplimiento será denunciado por daños y perjuicios. Todos los derechos están reservados, incluyendo
Some PV installations require the inverter to be connected to auxiliary equipment, such as solar radiation sensors,
aquellos que resulten de derechos de patentes o registro del diseño.
heat sensors, etc.
The orifices provided for this function can be opened by breaking the knock-out in the unit's base. Once the orifices
have been opened, they must be fitted with M12 and/or M20 metric cable glands which accept pipes of a diameter
La correspondencia del contenido del documento con el hardware ha sido comprobada. Sin embargo,
between 3.5 and 7 mm for PG 12 and between 7 and 13 mm for PG20.
pueden existir discrepancias. No se asume ninguna responsabilidad por la concordancia total. La infor-
mación que contiene este documento es revisada regularmente y es posible que se produzcan cambios
Once the connection has been made, check that the cable glands used have been "closed" appropriately to guar-
en siguientes ediciones.
antee sealing of the box.
A closure which is not sealed may allow moisture to enter and seriously damage the unit, invalidating the manufac-
turer's warranty in addition.
El presente documento es susceptible de ser cambiado.
If a knock-out which is not to be used is opened accidentally or one which has been fitted with a cable gland is no
longer used, these open orifices must be closed with a sealing plug which maintains the unit's hermetic seal.
See the Section «Hermetic closure of the unit».
5.3.5 Connection for communication over RS485 serial line
All INGECON SUN LITE units have communication over an RS485 serial line. As the RS485 communication
The copy, distribution or use of this document or of its content requires written authorisation. Any
board is already wired to the Harting HAN 4A female connector, simply plug in a male connector of the same type.
breach thereof will be reported for damages. All rights reserved including those of patent rights or
Refer to "AAX2002IKH01 Installation Guide for Communications Devices" for how to wire correctly the male con-
design registration.
nectors which need to be plugged into the connector on the inverter.
This connector can be supplied by Ingeteam if requested together with the unit.
The conformity of the document content with the hardware described has been checked. However,
discrepancies may exist. Liability will not be assumed for total concordance. The information contained

5.3.6 Connection for communication by other means

At the request of the installer, inverters may optionally incorporate hardware for communicating via:
in this document is regularly revised and it is possible that there may be changes in subsequent
- GSM/GPRS telephone
editions.Other functions may be available which are not covered by this document.
- Ethernet
In all these units, the auxiliary signals connect directly to the corresponding communications card.
This document may be changed.
See "AAX2002IKH01 Installation Guide for Communications Devices".

5.3.7 Connection to ground and to the electricity grid

The inverter's metal parts (unit ground) are electrically connected to the ground pin in the grid connection quick
connector.
To ensure the safety of personnel, this terminal must be connected to the installation's ground.
The connection of the grid Neutral and Phase to the inverter is made by means of a three-terminal connector.
The maximum diameter of the cable pipe permissible for the connector is 14 mm.
If the inverter and the grid connection point are far enough apart to require the use of cables of a greater section,
an external junction box close to the inverter to make this section change is recommended.