Screen 9
This screen displays a histogram of the power output from each of the inverters configured in the master-slave system.

9.5. Reasons for shutdown

This menu shows the last five inverter shutdowns, with reasons and corresponding date and time.
Meaning of reasons for shutdown:
MP VIN
MP FRED
MP VRED
MP VARISTORES
MP AISL.DC
MP INT AC RMS
MP TEMPERATURA
MP CONFIG
MP PARO MANUAL
MP B VPV MED
MP HW_DESCX2
MP IAC INST
MP CR.FIRMWARE
MP LEC ADC
MP CONSUMO POT
MP FUSIBLE DC
MP TEMP AUX
MP PROTECCION AC
MP MAGNETO AC
MP CONTACTOR
MP RESET_WD
MP LAT ADC
MP ERROR FATAL
MP FALLO RAMA1
MP FALLO RAMA2
MP FALLO RAMA3
MP PI CORR SAT
MP LATENCIA SPI
MP REDUNDANTE
MP PROTECCIÓN PIB
88
10:22
REASONS FOR SHUTDOWN
13:43 (08/01) -> MANUAL SHUTDOWN
17:22 (08/01) -> POT CURRENT
19:35 (07/01) -> POT CURRENT
12:21 (05/01) -> FRED
15:51 (04/01) -> POT CURRENT
High input voltage from the panels.
Incorrect grid frequency.
Incorrect grid voltage.
Varistor fault.
DC insulation fault.
Continuous overvoltage on AC output.
Overtemperature in the power electronics.
Shutdown for configuration change.
Manual shutdown.
Low input voltage from the panels.
Internal fault.
Voltage surge on AC output.
Shutdown due to firmware change.
AD converter (internal) reading fault.
Insufficient solar radiation. Does not trigger alarm.
Input fuse fault.
Redundant temperature sensor fault.
AC Protection.
Thermomagnetic circuit breaker error.
Contactor failed to close.
Stopped for Watch Dog reset (internal).
Converter (internal) fault.
Fatal error in the inverter.
Power electronics fault.
Power electronics fault.
Power electronics fault.
PI current saturation (internal).
Communication fault with redundant system.
The redundant system has caused a shutdown.
The PIB has caused a shutdown.
14/04/11
Installation manual
AAV2000IKI01