Ambient Temperature; Atmospheric Conditions; Contamination Class; Acoustic Contaminación - Ingeteam Ingecon Sun 250 TL Installation Manual

Table of Contents

Advertisement

Installation manual
Ingecon
Sun Power Max should therefore be installed in an enclosed, covered location.
®
The environment in which they are assembled should always be dry and free of dust.
They are not suitable for outdoor installation.

2.1.3. Ambient temperature

These units are designed to operate in a temperature range from -20 °C to 65 °C.

2.1.4. Atmospheric conditions

The ambient air must be clean and relative humidity must not exceed 50% at over 40 °C. Higher levels of relative
humidity, up to 95%, can be tolerated at below 30 °C.
It should be borne in mind that moderate condensation may occasionally occur as a consequence of temperature
variations. For this reason, apart from the unit's own protection, vigilance of these units is necessary once they have
been started up on sites where the conditions described above are not expected to be present.
In the event of condensation, never apply voltage to the unit.

2.1.5. Contamination class

The pollution class for which the units have been designed is grade 3.
Suitable measures should be taken to provide dust-free air of sufficient quality in the vicinity of the inverter.
2.1.6. Acoustic contaminación
When on, the inverter generates a buzzing sound.
Do not place it in an occupied room, or on light supports which might amplify this buzz. The mounting surface must
be firm and appropriate for the weight of the unit.

2.1.7. Ventilation

A minimum space of 20 cm must be maintained on both sides and in front of the unit to allow the free circulation of
air through the circulation vents.
Ingecon
Sun Power Max units have cooling fans on top of each cabinet containing an electronic
®
block. These fans start up for a few seconds each time the inverter is connected to the mains and is
about to inject power. This procedure makes it possible to easily check proper operation.
Fans require different air flow for cooling electronics, depending on the number of electronics units and the number
of unit cabinets. Always provide for each unit the flow values listed in the following table:
250 TL, 315HE TL, 365HE TL, 400HE TL, 420HE TL
375 TL, 500HE TL, 550HE TL, 600HE TL, 630HE TL
500 TL, 625HE TL, 730HE TL, 800HE TL, 840HE TL
Acceptable pressure loss is 34 Pa and air inlet velocity less than 3 m/s.
CAUTION
Do not place any object on top of the unit.
Avoid dropping particles that could enter the unit through air vents.
AAV2000IKI01
Model
Ingeteam Energy, S.A.
Airflow (m3/h)
2670
4640
5340
15