Dc Circuit Protections - Ingeteam Ingecon Sun 250 TL Installation Manual

Table of Contents

Advertisement

Ingeteam Energy, S.A.

8.4.5. DC circuit protections

Code
Alarm
0100H
AC protections
TACTOR SWITCH
In the event of a "0100H" alarm, check the status of the DC fuse branch. To check for proper status observe the
following:
Continuity between terminals X7x.1 and X1.1.
Continuity between X1.1 and J19.1.
See illustrations on page 76.
78
Reason for shutdown
DC fuses
CONT:
THERMAL CON-
Blown DC input fuse or DC arresters.
CONTROL HW
Installation manual
Description
AAV2000IKI01