Handling Tasks; Personal Protection Equipment (Ppe) - Ingeteam Ingecon Sun 250 TL Installation Manual

Table of Contents

Advertisement

Installation manual

4.4.3. Handling tasks

Definition: Tasks involving the assembly and/or replacement of parts as well as changes to the setting of panel com-
ponents. Any task that does not fall under Inspection or Control is considered Handling.
It is always necessary to fir disconnect and check for absence of voltage.
The "5 Golden Rules" must be adhered to.
5 GOLDEN RULES
1.
Disconnect
Switching on the possible voltage sources. Bear in mind that any capacitors or other elements pow-
ered from uninterruptible power supplies (UPS) are still live.
2.
Prevent any possible feedback
The switching devices used to switch off the equipment must be protected against any possible
disconnection.
3.
Check there is no voltage
Check that there is no voltage in all the active elements of the electrical system or as close as pos-
sible to the work area.
4.
Ground and short circuit
In the low voltage installations that by induction or for other reasons may be accidentally live. And
always in high voltage installations.
5.
Rope off and mark the work area

4.4.4. Personal Protection Equipment (PPE)

Inspection
The use of safety footwear to standard EN 345-1:1992 is mandatory and work clothing should be cotton and be free
of conductor/metallic elements.
Control
The use of helmets compliant with standard EN 397:1995 and safety footwear compliant with standard EN 345-
1:1992 is mandatory. The use of standard safety gloves is also mandatory for voltage-free tasks.
It is also mandatory to use dielectric gloves meeting standard EN-60903-1992 and protective face mask against
electric shock for voltage testing tasks and opening or closing automatic switches under load (IP2x).
Handling
The use of helmets compliant with standard EN 397:1995 and safety footwear compliant with standard EN 345-
1:1992 is mandatory.
It is also mandatory to use dielectric gloves meeting standard EN-60903-1992 and protective face mask against
electric shock for voltage testing tasks and opening or closing automatic switches under load (IP2x).
AAV2000IKI01
Ingeteam Energy, S.A.
29