8.4.2. Temperature

Code
Alarm
0002H
Temperature
In the event of a shutdown with reason "Motivo_Paro_Temperatura", the first step is to check if the 0020H alarm
persists. If so, check the temperature of the unit's radiator via the display menu:
If the temperature displayed is close to or above 80 degrees, the unit has failed to inject power as a precau-
tion against a potentially damaging radiator temperature for the unit. The inverter will remain in this state until the
radiator has cooled, and then it will reconnect to the network.
If the problem occurs frequently, you should check the ventilation (fans and air intake grills) of the inverter and the
enclosure in which it is installed.
72
Reason for shutdown
Power electronics temperature.
Auxiliary temperatura sensor
MONITORING
Intake board
The power electronics exceeds 80 °C
The auxiliary temperature sensor has triggered an alarm
Installation manual
Description
TempRad
AAV2000IKI01