Connection For Communication Via Modem-Gsm/Gprs + Rs-485 - Ingeteam Ingecon Sun 250 TL Installation Manual

Table of Contents

Advertisement

Ingeteam Energy, S.A.
Connection for communication via RS-485 serial port
Ingecon
Sun Power Max units incorporate hardware for communicating through an RS-485 serial line. This hardware
®
comprises two to four "AAP0022 Com RS-485" boards (one per module) that are supplied mounted on the control
board in each power block, the communications terminal strip and the wiring between boards and terminal strip.
Thanks to this pre-installation, the installer will only need to make the connection via the terminal, located as shown
in the following figure in the DC module at the top of the sidewall.
To access this terminal, use the access openings in this area of the enclosure.
The unit is provided with a 211 Ohm ferrite rod. The cable connecting the "AAP0022 Com RS-485"
board of the first inverter to the terminals must be inserted as close as possible to the board, turning
it around the centre hole twice.
For more information on board operation, see "AAX2002IKH01 Installation Guide for Communications Devices".

5.4.7. Connection for communication via modem-GSM/GPRS + RS-485

At the request of the installer, inverters may optionally be equipped with hardware for communication via GSM/GPRS
phone. This hardware comprises one to three "AAP0022 Com RS-485" boards (one per module except for module
1) that are supplied mounted on the control board in each power block, a "AAX0001 Com GSM/GPRS + RS-485"
board (for module 1), the rod for the modem, the communications terminal strip and the wiring between boards and
terminal strip.
The unit is provided with a 211 Ohm ferrite rod. The cable connecting the "AAX0001 Com GSM/
GPRS + RS-485" board of the terminal (RS-485 output) must be inserted as close as possible to
the board, turning it around the centre hole twice.
The board is provided assembled on the control board and a bag (attached with a plastic tie) containing the rod cable.
Connect the rod cable to the cable's rod output, and feed it out through the holes on the upper left side of the enclo-
sure. Connect the end that goes outside to the rod and attach it via its magnet to the unit's enclosure.
50
Location of communication accessories wiring holes
Installation manual