D40 tapered grommet.
Power access and PV array
connection.
Access points common to all Ingecon
Access for communication cables or auxiliary inputs is located on the left side of the DC cabinet in all versions.
Each gland allows for a range of cable diameters:
The tapered grommets allow wire diameter of up to 40 mm.
Care must be taken to ensure the equipment is not live when accessing its interior.
All the doors on the cabinet are arranged so that they can only be opened when the AC
thermomagnetic circuit breaker, the DC circuit breaker and any auxiliary external supplies are
disabled.
When checking that there is no voltage, wearing dielectric gloves and safety goggles approved for
electrical hazards is required.
While the door is open, do not alter the position of the thermomagnetic or CD circuit breaker, do not operate the con-
trols on the door nor apply force to the internal electrical devices which they control.
They must also be in the OFF position for the door to be able to be closed.
After setting the AC thermomagnetic circuit breaker, the DC circuit breaker and any auxiliary external supplies to OFF,
wait at least 10 minutes before opening the door. Internal capacitances may still hold hazardous voltages.
AAV2000IKI01
D40 tapered grommet. Power access, grid connection and free
multi-purpose access.
Sun Power Max units
®
Gland diameter (mm)
40
16
12
Bottom view
Cable diameter (mm)
19 ~ 28
4.5 ~ 10
3.5 ~ 7
Ingeteam Energy, S.A.