HANDLING PRECAUTIONS
Segment
1
Segment
1
Repeat on/off and return destination are set by the segment with the segment number
and repeat count. Operation completes at the end of a segment. If there is a repeat set-
ting, the program returns to the start of the set destination segment and operation is
resumed from there. This operation is repeated the number of times specified by the
repeat count.
Segment
Segment
1
2
No repeat is performed when the destination segment number is larger than the current
segment number. When the program returns to the first segment, PV is not started even
if a PV start setting has been made.
• When repeat operations involve multiple segments and the destination seg-
ment settings overlap, nest or intersect, the repeat operation will become an
abnormal eternal loop. Do not make such settings.
Segment
Segment
3
2
Example of a double
Segment
Segment
2
3
Intersect example 1
• When the current segment does not contain a set value or the value is 0, exe-
cuted values for program items (for example, set PV event values or set PID
group selection values) that are sequels to settings in a previous segment are
the same during the first run and the repeat run.
Segment
Segment
4
3
Segment
Segment
1
Example of a nest
Segment
Segment
4
Chapter 5. FUNCTIONS
Segment
Segment
2
3
Segment
Segment
1
2
Intersect example 2
4
3
5-19