Honeywell DCP551 Mark ΙΙ User Manual page 221

Digital control programmer
Table of Contents

Advertisement

Setup data setting
No.
Item code
C 01
1
PV1 range number
C 02
2
PV1 temperature unit
C 03
3
PV1 decimal point position
C 04
4
PV1 linear decimal point position 1
C 05
5
PV1 linear range lower limit
C 06
6
PV1 linear range upper limit
C 07
7
PV1 cold junction compensation
C 08
8
PV1 root extraction
C 09
9
PV1 root extraction dropout
C 10
10
PV1 cold junction bias
C 11
11
PV2 range number
C 12
12
PV2 temperature unit
C 13
13
PV2 decimal point position
C 14
14
PV2 linear decimal point position 1
C 15
15
PV2 linear range lower limit
C 16
16
PV2 linear range upper limit
C 17
17
PV2 cold junction compensation
18
C 18
PV2 root extraction
C 19
19
PV2 root extraction dropout
C 20
20
PV2 cold junction bias
C 21
21
Control output system
C 23
23
Control action
C 25
25
PV channel switching type
C 26
26
PV channel switching system
C 27
27
PV channel switching point
C 28
28
PV channel switching dead band 100 PVU
denotes items settable only on models with two PV input channels.
Item
Factory default
settings
0
0
1
0 PVU
10000 PVU
0
0
0.2
0.0
0
0
1
0 PVU
10000 PVU
0
0
0.2
0.0
1
0
0
0
10000 PVU
DCP551 Parameter Work Sheet
User
Settings and descriptions
-
settings
0 to 16
: Thermocouple
48 to 52
: Linear (DC current and DC voltage)
64 to 71
: Resistance temperature detector
96 to 103 : Resistance temperature detector
128 to 134: Linear (DC current and DC voltage)
0 : Celsius (°C)
1 : Fahrenheit (°F)
0 to 2
0 to 4
–19999 to +20000 PVU(PV1)
–19999 to +20000 PVU(PV1)
0 : Provided (Compensated inside the instrument)
1 : Not provided (Compensated outside the instrument)
0 : Not provided
1 : Provided
0.2 to 10.0% (Ratio to input range)
–1.0 to + 1.0°C
0 to 16
: Thermocouple
48 to 52
: Linear (DC current and DC voltage)
64 to 71
: Resistance temperature detector
96 to 103 : Resistance temperature detector
128 to 134: Linear (DC current and DC voltage)
0 : Celsius (°C)
1 : Fahrenheit (°F)
0 to 2
0 to 4
–19999 to +20000 PVU(PV2)
–19999 to +20000 PVU(PV2)
0 : Provided (Compensated inside the instrument)
1 : Not provided (Compensated outside the instrument)
0 : Not provided
1 : Provided
0.2 to 10.0% (Ratio to input range)
–1.0 to + 1.0°C
0 : 5S output (Current proportional SP output)
1 : 5G output (Current proportional control output)
2 : 6D output (Voltage time proportional control output) system A
3 : 6D output (Voltage time proportional control output) system B
4 : 8D output (open collector time proportional control output) system A
5 : 8D output (open collector time proportional control output) system B
0 : PID — A reverse operation
1 : PID — A normal operation
2 : PID — B reverse operation
3 : PID — B normal operation
0 : PV1 low-temperature sensor, PV2 high-temperature sensor
1 : PV1 high-temperature sensor, PV2 low-temperature sensor
2 : PV1 tied
3 : PV2 tied
4 : Backup switching
0 : External switch switching
1 : Automatic switching (switching + dead band)
2 :
Automatic switching B (switching + dead band + external switch)
3 : Automatic switching C (2-point proportional)
–19999 to +20000 PVU(PV1)
1 to 1000 PVU(PV1)
11